Installation Manual

Programming Sheets
70
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
83
Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
84
Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio.
85
Output Relay #1 Enable. '0' to disable relay.
86
Output Relay #1 Function Selection. '0' for activation on fire alarm (2-wire smoke).
87
Output Relay #2 Enable. '0' to disable relay.
88
Output Relay #2 Function Selection. '2’ for activation on DACT trouble.
89
Reserved for future use. Leave default setting of ‘0.’
90
Reserved for future use. Leave default setting of ‘0.’
91
Alarm Verification. '0' to disable.
92
Silence Inhibit. '0' to disable.
93
Autosilence. '0' to disable.
94
Restoral Method. '0' for Typical restoral.
95
Coding, Notification Appliance Circuit. '0' for no coding.
96
Trouble Call Limit - Dialer Runaway Prevention Feature. '0' for disabled feature.
97
98
99
100
Future Use.
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
Addresses 101 to 120 store the Service Terminal 1 Phone Number. Valid entries are 0 - 9 and A
- E. 'F' designates the end of the phone number.
121
122
Ring Count on Primary Phone Line. '03' for number of rings before answering call.
123
FAX/Answer Machine, Primary Phone Line. '0' for no sharing of phone line.
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
Addresses 124 to 143 store the Service Terminal 2 Phone Number. Valid entries are 0-9 and A-E. 'F'
designates the end of the phone number.
144
Upload/Download Backup Reporting. '0' for Upload/Download reports to go to the Secondary Central Sta-
tion Phone Number on backup only.
0
0
0
0
0
2
0
0
0
0 0 0 0