Install Instructions
GETTING
STARTED
Application Considerations
Electrical Power / Airow Switch
The Honeywell Enhanced Air Cleaner should only be powered when airow is present.
1620/2020/2520 – These models are designed for use with an air handler and are equipped with an airow
switch (see Fig. 1), which provides power only when the air handler blower is operating. These models are
designed to be powered from a 208 to 230 VAC single phase power source.
M28899
Fig. 1. Airow Switch.
1625/2025 – The furnace control EAC terminals provide power to the unit only when the furnace blower is
operating. These models are designed to be powered from the electronic air cleaner (EAC) terminals on a
furnace control board. If EAC terminals are not available, an alternative airow sensing mechanism must be
used to ensure the Honeywell Enhanced Air Cleaner is only powered when airow is present. Contact your
local Honeywell distributor for information on alternatives.
TrueCLEAN™ Enhanced Air Cleaner 68-0308EFS—01
4