Installation Instructions

- 2 -
3. Mount the Sensor
[A] = Fixed mounting holes
[B] = Adjustable mounting slots from 61mm-85mm (2.4-3.3)
[C] = Tamper hole
*This accessory is not covered by the approval.
4. Wire the Sensor
Wiring Details
Observe proper polarity.
If not using the integrated EOL resistors, set all switches to OFF.
If using the integrated EOL resistors:
1. Connect the sensor to the panel.
2. Set the appropriate Alarm, Tamper and Trouble/Anti-mask EOL
DIP switches to ON. (see Step 5 ).
Notes:
Consult the Control Panel manual to determine
proper EOL selection.
The Alarm, Tamper and Trouble/anti-mask EOL
settings must each only have one switch ON.
The EOL values should be set at the same time.