Installation Manual
- 3 -
LED
Power
Up
Walk Test Normal Trouble
Red
Slow
Blink
ON
Alarm
ON
Alarm
Fast
Blink
Yellow OFF
ON
Microwave
ON
Microwave
OFF
Green OFF
ON
PIR
ON
PIR
OFF
Zones
A
2
Look-down
B
18
Lower
C
46
Intermediate
D
36
Long
1. Apply power to the sensor. Initialization is complete when the LED stops
flashing slowly (about 30 seconds).
2. Turn the microwave sensitivity counterclockwise to reduce the microwave range
(minimum = 16.4’ / 5m) and close the sensor.
3. Walk through the detection area and observe the LED.
4. Adjust the microwave range as necessary to meet installation requirements.
Walk test mode is active for 10 minutes, then automatically exits test mode, disables the LED and enters
normal operation mode. For an additional 10 minute walk test, enable walk test mode again with the
flashlight feature:
Note: During power up and walk test modes the LED is active regardless of the LED Enable/Disable DIP switch setting.
Flashlight Feature:
1. Use a flashlight with a bright light beam, and stand within 4’ (1.2 m) of the sensor.
2. Swing the light beam past the sensor IR window 3-5 times, holding the beam
on the window for 0.5 second each pass.
The flashlight feature is only available for the first 24 hours after the first power up.