Installation Information
Terminal Description
* NOTE: The outer screws on each 
terminal block secure the block to the 
chassis. They are not used for wiring.
The six terminals for the left hand terminal block are:
 FLOAT (2): External low-voltage water sensor or float 
switch
  DHUM:  Compressor and fan operation for 
dehumidification
  R:  DR65 24V output
  FAN:  Fan activation only for ventilation
  C:  DR65 24V output
External 24V devices can be powered from R and C 
terminals (20VA max.)
The right hand terminal block in the above 
figure is used only for interlocking a TrueDry 
DR65 with an equipment fan. The three 
terminals are:
  Gt:  Fan operation from thermostat
  Rf:  24V from equipment fan
  Gf:  Fan operation from equipment fan
Wiring
Wire the TrueDRY 
DR65 according to 
the diagram that 
applies to your 
desired operation.
Follow this diagram for 
ducted operation with the 
onboard dehumidistat.
Two wiring terminal blocks are located on the exhaust end of the TrueDRY unit.
TrueDRY
HVAC
THERMOSTAT
GYWRRc
GYWR C
M33153
Gt
+
+
Rf
Gf
DHUM
+
+
R
FAN
C
FLOAT FLOAT
TrueDry DR65 Dehumidication System 69-2089EFS—12 7
CAUTION: Low voltage hazard.
Can cause equipment damage.
Disconnect HVAC equipment before beginning installation.