Installation Information
Troubleshooting (continued)
Problem Recommended Troubleshooting Steps
Fan does not run with 
ventilation activated. 
Compressor runs briefly 
but cycles on & off with 
humidity control turned to 
ON.
1.  Loose connection in fan circuit.
2.  Obstruction prevents fan rotation.
3.  Defective fan.
4.  Defective fan relay.
5.  Defective fan capacitor.
Evaporator coil frosted 
continuously, low de-
humidifying capacity.
1.  Defrost thermostat loose or defective.
2.  Low refrigerant charge.
3.  Dirty air filter(s) or airflow restricted.
Unit not providing 
ventilation.
1.  Check control wire connections (check connections at fresh air damper 
also).
2.  Defective fresh air damper.
3.  Dirty air intake. Clean outside intake hood.
Unit removes some 
water, but not as much as 
expected.
1.  Air temperature and/or humidity have dropped.
2.  Humidity meter and or thermometer used are out of calibration.
3.  Unit has entered defrost cycle.
4.  Dirty air filter.
5.  Defective defrost thermostat.
6.  Low refrigerant charge.
7.  Air leak such as loose cover or ducting leaks.
8.  Defective compressor.
9.  Restrictive ducting.
10. Optional Condensate Pump Safety Switch open.
Unit Test to determine 
problem:
1.  Detach field control wiring connections from main unit.
2. ConnecttheRandFANcontactsfromthemainunittogether;onlythe
impeller fan should run. Disconnect the wires.
3. ConnecttheRandDHUMcontactsfromthemainunittogether;the
compressor and impeller fan should run.
4.  If these tests work, the main unit is working properly. You should check 
the control panel and field control wiring for problems next.
5.  Remove the control panel from the mounting box and detach it from the 
field installed control wiring. Connect the blue, yellow, and green wires 
from the control panel directly to the corresponding colored pigtails on 
the main unit. Leave the violet, white, and red wires disconnected!
6.  Turn on the humidity control. The compressor and impeller fan should 
run.
7.  If these tests work, the problem is most likely in the field control wiring.
Refrigerant Charging
If the refrigerant charge is lost due to service or a leak, a new charge must be accurately weighed in. If any 
of the old charge is left in the system, it must be recovered before weighing in the new charge. Refer to the 
unit nameplate for the correct charge weight and refrigerant type.
TrueDry DR65 Dehumidication System 69-2089EFS—12