NOTHERM T8611G Owner's manual

T8611G CHRONOTHERM
®
DELUXE ZONING HEAT PUMP THERMOSTAT
7 69-1414—2
IMPORTANT
Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. The thermostat has saved the
Installer Setup changes and initiated a reset in
order to operate using the new settings. Be sure
to set the current day and time immediately.
Temperature
display
adjustment.
37 0 No difference in
displayed
temperature and
actual room
temperature.
3 thru -3
or
1.5 thru
-1.5
1 (0.5)—Display adjusts to
1°F (0.5°C) higher than
actual room temperature.
2 (1.0)—Display adjusts to
2°F (1.0°C) higher than
actual room temperature.
3 (1.5) —Display adjusts to
3°F (1.5°C) higher than
actual room temperature.
-1 (-0.5) —Display adjusts to
-1°F (-0.5°C) lower than
actual room temperature.
-2 (-1.0) —Display adjusts to
-2°F (-1.0°C) lower than
actual room temperature.
-3 (-1.5) —Display adjusts to
-3°F (-1.5°C) lower than
actual room temperature.
Furnace Air
Filter Timer.
43 2 30 days (System
run time)
0, 1, 3, 4 0 – off
1 – 10 days
3 – 60 days
4 – 120 days
(Time is counted when heat,
cool or fan is running.)
Humidifier Pad
Monitor.
44 0 Off 1, 2, 3 1 – 90 days
2 – 180 days
3 – 365 days
(Time is counted by calendar
days in heat mode.)
Ultraviolet (UV)
Air Treatment
System Lamp
Monitor.
45 0 Off 1 1 – 365 days
(Time is counted by calendar
days in any mode.)
Table 4. Thermostat Installer Setup Options. (Continued)
Select
Installer Setup
Number (Press
Time key to
change)
Factory Setting
Other Choices
(Press or key to change)
Actual
SettingDisplay Description Display Description