Table 8. T8611G2051 Sequence of Operation.
Table 9. Occupied Terminal Operation.
Fan
Selection System Selection Call Energize Display****
AUTO OFF None None None
AUTO OFF Fan G Fan Symbol
ON OFF None G Fan Symbol
AUTO COOL None O* None
AUTO COOL or AUTO Cooling O, G, Y Snowflake Symbol,
Fan Symbol
AUTO HEAT or AUTO None B* None
AUTO HEAT or AUTO Stage 1 Heating B, Y Flame Symbol,
Fan Symbol
AUTO HEAT or AUTO Stage 2 Heating B, Y, W2 Flame Symbol,
Fan Symbol,
AUX. HEAT
AUTO EM. HEAT None L EM. HEAT
AUTO EM. HEAT Stage 1 Heating L, E Flame Symbol,
Fan Symbol,
EM. HEAT
AUTO EM. HEAT Stage 2 Heating L, E, W2 Flame Symbol,
Fan Symbol,
EM. HEAT,
AUX. HEAT
AUTO AUTO None O**, B*** None
SYSTEM and FAN selection identified on the LCD.
* = Thermostat O/B terminal is configurable for heating or cooling changover.
** = O is energized when cooling was last call from thermostat.
*** = B is energized when heating was last call from thermostat.
**** = Installer setup mode 36 disables flame and snowflake icons from display.
Mode OC Contacts Closed Display
Wake No None
Leave Yes None
Return No None
Sleep Yes None