Owner's Manual

Page 4 of 6 — HON-62044:A • 08/31/2020
Figure 1 illustrates the setup for a typical BDA System Riser.
Figure 1 Typical BDA System Riser Diagram
ORDERING INFORMATION
Signal Boosters / Bi-Directional Amplifiers (BDA)
HON
-BDA400-D5-1A:
Class A, UHF Digital BDA,
406.1
512MHz, 5W
,
Honeywell
HON
-BDA400-D5-1B
: Class B, UHF Digital BDA,
406.1
512MHz, 5W
,
Honeywell
HON
-BDA800-D5-1A
: Class A, 800MHz Digital BDA, 5W
,
Honeywell
HON
-BDA800-D5-1B:
Class B, 800MHz Digital BDA , 5W,
Honeywell
HON
-BDA7800-D5-2A:
Class A, 700MHz & 800MHz Dual Band
Digital BDA, 5W
,
HON
-BDA7800-D5-2B:
Class B, 700MHz & 800MHz Dual
Band Digital BDA, 5W
,
Honeywell
Batteries and Battery Enclosure
BDA-EPSU-300A-ASSY:
Battery backup / external power
supply for BDA, Type-4 certified enclosure.
BDA-EPSU-300A:
External power supply only for BDA, excludes
enclosure.
Batteries and Battery Enclosure (Continued)
BDA-ENCL-15UL4:
Battery Backup Enclosure assembly only,
excludes power supply.
BDA-BB-75-10:
Battery, 12V/75Ah each. (minimum two are
required for each
BDA/signal booster).
Cable, Connectors, and Lightning Arrestors
BDA-CABLE-10A-250:
250 ft. Cable, Red Jacket, Imprinted, 1/2"
Corrugated Alum Plenum Air Dielectric, 50 Ohm Coaxial.
BDA-CABLE-10A-500:
500 ft. Cable-Black Jacket, Imprinted, 1/4”
Corrugated Copper Foam Dielectric, 50 Ohm Coaxial.
BDA-CABLE-15A-250:
250 ft. Cable
-
Black Jacket, Imprinted,
1/4"
Corrugated Copper Foam Dielectric, 50 Ohm Coaxial.
BDA-CABLE-15A-500:
500 ft. Cable
-
Black Jacket, Imprinted,
1/4"
Corrugated Copper Foam Dielectric, 50 Ohm Coaxial.
BDA-NMC-10:
N-Male Connector for 1/2" cable.
BDA-NFC-11:
N-Female Connector for 1/2" cable.
BDA-NMC-40A:
N-Male connector for 1/4" Cable.
BDA-NFC-41A:
N-Female connector for 1/4" Cable.
Donor Antenna Direction-S/SE
Antenna mast to be bonded to building steel
Lightening-Arrestor, Grounded
Located outside before the cable building entry.
Roof
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
8-conductor:18-24GA cable
To be supplied and installed
by the Electrical Contractor.
BDA status annunciator,
mounts on a standard,
4-2-gang electrical box.
Box supplied and installed by
the EC.
Located at the building entrance
or other location designated by
AHJ.
2 110V
Emergency
circuits
24 V
Battery
Backup
BDA
1/2 Plenum Rated
Coaxial Cable
Connect to the fire alarm panel,
5 Supervisory Modules required.
BDA Antenna Failure
BDA Trouble
BDA Power Loss
BDA Charger Trouble
BDA Low Battery
Note 1:
1.-The EC and EE/Architect shall review
and approve the proposed equipment,
cable riser locations and fire survivability
requirements.
Note 2:
Where required, the BDA and the coaxial cable
shall be located in a 2-hour fire rated space.
firealarmresources.com