MECHANICAL AND ENVIRONMENTAL SPECIFICATIONS
Table 2 lists the mechanical and environmental specifications for each BDA model.
PSU (BDA-EPSU-300A-ASSY) Technical Specifications:
Table 3 lists the PSU Technical Specifications.
PSU Connections:
Table 4 lists the PSU Connections.
Batteries and Battery Enclosure
• NEMA-4, UL Type-4 Listed Battery Enclosure
• 12V / 75Ah battery, minimum two are required for each BDA .
Donor Antennas
• Installed on the Roof of the building.
•
Pointing to the public safety radio repeater site, line of sight not
required.
• High gain, high directivity Yagi Antennas for various frequency
bands.
DAS Antennas
• Installed in-building based on the design to achieve coverage.
• Fiberglass and Low Profile antennas for various frequency bands.
Coaxial Cable
• Plenum Rated, ½” diameter with low insertion loss.
• Red cable color to differentiate for Public Safety BDA use.
Connectors and Lighting Arrestors
• Various types of connectors, cable jumpers for ½” cable.
• Coaxial surge protector, UL listed.
• Cable jumper and Antenna Sensor / EOL termination for Donor
Antenna.
Power Dividers and Hybrid Couplers
• 2/3/4-way power dividers for various frequency bands.
• Directional couplers for various dB and Frequency bands.
Services
• Services for BDA iBwave System Design, Drawings, BOM.
• Services for BDA Training
Specification
HON-BDA400-D5-1A HON-BDA400-D5-1B HON-BDA800-D5-1A HON-BDA800-D5-1B HON-BDA7800-D5-2A HON-BDA7800-D5-2B
Enclosure
Environmental
Rating
NEMA-4 (Type-4) NEMA-4 (Type-4) NEMA-4 (Type-4) NEMA-4 (Type-4) NEMA-4
(Type-4)
NEMA-4 (Type-4)
Dimensions
(WxDxH)
23.23”x8.32” x24”23.23”x8.32” x24”23.23”x8.32” x24”23.23”x8.32” x24”23.23”x8.32” x25.4” 23.23”x8.32” x25.4”
Weight (With
Duplexers)
Typ. (lbs)
<59<59<59<59<59 <59
Enclosure Color Red (RAL3000) Red (RAL3000) Red (RAL3000) Red (RAL3000) Red (RAL3000) Red (RAL3000)
Operating
Temperature
°F (°C)
-22 to +140
(-30 to +60)
-22 to +140
(-30 to +60)
-22 to +140
(-30 to +60)
-22 to +140
(-30 to +60)
-22 to +140
(-30 to +60)
-22 to +140
(-30 to +60)
Recommended
Operating
Environment
Temperature
°F (°C)
-14 to +86
(-10 to +30)
-14 to +86
(-10 to +30)
-14 to +86
(-10 to +30)
-14 to +86
(-10 to +30)
-14 to +86
(-10 to +30)
-14 to +86
(-10 to +30)
Table 2 Mechanical and Environmental Specifications
Specifications Settings
AC In 100 – 250V / 50-60Hz / 3A @ 120V
DC Out 28.5V / 7A Continuous Duty
Charging Current 5.5A
Supervisory Functions AC, Battery Capacity, Battery V,
Charging Current, Load Presence,
Temp, MCU PSU Diagnostic, V out,
I out
Protection DC Out and Charger Electronic
Current Limiting + ATC Mini Fuse.
AC Input Fuse
Operating Temperature -22 to +140 °F (-30 to +60 °C)
Enclosure Environmental
Rating
NEMA-4 (Type-4, Waterproof
UL Listed)
Enclosure Dimensions 24”W x 10”D x 24”H
Weight with PSU,
without batteries
51 lbs.
Table 3 PSU Technical Specifications
Component Connections
Enclosure Connections Requires NEMA-4 Waterproof Conduit
AC Power Connection Built-In Duplex Power Outlet Included
DC Connection Wire Terminal Included
(10-14AWG Wire)
Battery Connection Fuse and Wire Harness Included
Supervisory CAT-5 Jumper to BDA
Table 4 PSU Connections