Install Instructions
C7600B, H7655A SOLID STATE HUMIDITY SENSORS
3 63-2166—8
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Location
The sensor cay be installed directly on a wall or standard wall
outlet box.
The sensor should be located away from traffic areas, on an
inside wall, at least 3 ft (1m) from an outside wall and 54 in.
(1.4m) from the floor.
Mounting
1. Loosen the cover locking screw and remove the cover.
2. Run wire to the selected location; thread wire through
the semicircular hole in the wallplate; and make
connections to the sensor (see the Wiring section).
3. Four mounting screws are provided, two self-tapping
type for wall mounting and two for outlet box mounting.
Select the proper screws for the application.
4. If air drafts occur through the wall opening, eliminate
with suitable material.
5. Fasten the sensor on the wall or outlet box with screws
through the wallplate mounting holes. See Fig. 4.
6. Replace the cover and tighten the cover locking screw.
Fig. 4. Mounting the sensor on an outlet box.
Operation
C7600B
The sensor provides a 2 to 10 Vdc output signal directly
proportional to the humidity of the air where the unit is
mounted.
H7665A
The sensor provides a 0 to 10 Vdc output signal directly
proportional to the humidity of the air where the unit is
mounted.
WIRING
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
See Fig. 5 through 9 for wiring details. Wire input power
(16 to 40 Vdc or 16 to 30 Vac) to V+ and GND terminals.
Connect sensor output (OUT) and GND to a controller analog
input as shown in Fig. 5 through 9.
Fig. 5. C7600B, H7655A typical wiring.
Fig. 6. C7600B wiring to W7620.
THERMOSTAT
MOUNTING
TAB SLOT (2)
MOUNTING
TAB
(2 INSIDE
COVER)
MOUNTING
SCREW (2)
COVER
LOCKING
SCREW
OUTLET BOX
M17719
WALLPLATE
HUMIDITY
SENSOR
~V+
GND
OUT
CONTROLLER
ANALOG
INPUT
SIG
GND
+
–
M2025E
24 Vac
120 Vac
L1
L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
C7600B
-V+
GND
OUT
M8809B
24 Vac
120 Vac
V1 (ANALOG INPUT)
COMM
W7620 (W7600)
L1
L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.