Instruction Manual

C7100A,B,C,D AVERAGING TEMPERATURE SENSORS
62-0214 2
Fig. 2. C7100 duct or plenum mounting.
Fig. 3. C7100 junction box mounting.
WIRING
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can
introduce disruptive electrical interference
(noise).
Keep wiring at least one foot away from large
inductive loads such as motors, line starters,
lighting ballasts, and large power distribution
panels.
Shielded cable is required in installations where
these guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Connect low voltage wiring from the sensor to the
appropriate system component terminals using 1/4 in.
(6 mm) female quick-connectors at both ends. See Fig. 4
and 5.
Fig. 4. Connecting C7100B for economizer,
mixed air and deck temperature sensing.
Fig. 5. Connecting C7100D to Excel 500 Control
System.
M21005
AIRSTREAM
M21006
2 X 4 INCH
JUNCTION BOX
MOUNTING
HOLES (4)
REAR 7/8 INCH
KNOCKOUT
C7100 AVERAGING
DISCHARGE SENSOR
M20050
C7100B
MIXED AIR
SENSOR
C7100B
COLD DECK
SENSOR
C7100B
HOT DECK
SENSOR
21
HOT DECK HIGH LIMIT–A7
3456
90
110
130 NO JUMPER
78
24 Vdc
W7081
LIMIT CONTROLLER
21
COLD DECK LOW LIMIT–A6
3456
45
55
60 NO JUMPER
21
ECONOMIZER/MIXED AIR LOW LIMIT–A5
3456
50
55
60 NO JUMPER
TO H205
ENTHALPY
CONTROLLER
TO W7080
LOAD
ANALYZER
+
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
AI 1
AI 2
AI 3
AI 4
AI 5
AI 6
AI 7
AI 8
1
2
1
2
C7100D XF521A/XF526
M2828
+10V