INSTALLATION INSTRUCTIONS
62-0214
C7100A,B,C,D
Averaging Temperature Sensors
APPLICATION
The C7100A,B,C,D Averaging Temperature Sensors 
provide the input required by the W7080, W7100, Excel 
500, and T775 Control Systems to sense temperature in 
discharge, hot deck, cold deck or return air.
Fig. 1. Approximate dimensions of C7100 Averaging Temperature Sensor in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
The sensor assembly (see Fig. 1) consists of an 
aluminum sensor probe (element housed internally) with 
attached flange that can bc mounted on a flat duct or 
plenum surface, or in a 2 by 4 in. (51 by 102 mm) 
junction box using four No. 8 screws. Connections to the 
sensor are made through two recessed 1/4 in. (6 mm) 
quick-connect terminals.
Location
The sensor should be located in the air duct or plenum 
where it will sample an average air temperature. Avoid 
locations where air stratification can cause sensor errors.
Mounting
Flat Duct or Plenum Surface Mounting (See Fig. 2)
1. Cut a 7/8 in. (22 mm) hole in the duct or plenum 
surface at the desired location.
2. Insert sensor probe into the duct or plenum with 
inlet holes facing the air stream.
3. If necessary, use the flange as a template to mark 
and drill four holes for No. 8 mounting screws.
4. Fasten the sensor to the duct or plenum surface 
with four No. 8 sheet metal screws (not provided).
Junction Box Mounting (See Fig. 3)
1. Cut a 718 in. (22 mm) hole in the duct or plenum 
sulfate at the desired location.
2. Remove the center rear knockout from the junction 
box and insert the sensing probe through the 
knockout with the flange flat against the junction 
box.
3. Using the flange as a template, mark and drill four 
holes in the junction box and the duct or plenum 
surface for No. 8 mounting screws.
4. Insert sensor probe through both the junction box 
knockout and the 7/8 in. (22 mm) hole drilled in the 
duct or plenum and fasten the junction box and 
sensor to the duct or plenum surface.
3/4
(19)
13-1/4 (336)
1-3/16
(30)
1-3/16
(30)
1-13/16
(46)
1-13/16
(46)