Product Manual

Appendix C
Standard Certifications
The BW Clip4 gas detector is in conformity with the following standards:
ANSI/UL 61010-1-2016, 3rd ed
ANSI/UL 60079-0-2013 (R2017)
ANSI/UL 60079-11-2013 (R2018)
ANSI/UL 913-2015
1
CSA C22.2 No. 0-10 (R2015)
CSA C22.2 No. 152-M1984 (R2016)
CSA C22.2 No. 60079-0-15 (R2018)
CSA C22.2 No. 60079-11-14 (R2018)
CSA C22.2 No. 61010-1-12 (R2017), 3rd ed
EN 60079-0:2018
EN 60079:11:2012
IEC 60079-0:2017 ed. 7
IEC 60079-11:2011 ed. 6
1
BW Clip4’s flammable sensor was evaluated for CSA C22.2 No.152-M1984 (R2016).
The evaluation was valid only with the calibration flow rate 300 ml/min and CH4 gas. The
other flow rate for calibration and other ammable gases are not the scope of CSA C22.2
No.152-M1984(R2016). In accordance with CSA C22.2 No. 152-M1984 (R2016), the
adjustable alarm point shall not exceed 60% LEL. BW Clip4’s flammable sensor opera-
tional limitations are:
Storage temperature: −40 to +55°C
Operational temperature: −40 to +55°C (Intermittent)
Humidity: 0 to 95% R.H. (non-condensing)
Air velocity: lower than 300 m/min
If BW Clip4’s flammable sensor is suspected to be damaged by aggressive substances,
please Perform Bump Test and Calibration per this manual.
CSA (CSA18CA70205765)
Classified by CSA to both US and Canadian Standards as intrinsically safe for
Class I, Division 1, Group A, B, C, D and Class I, Zone 0, Group IIC, −40°C
Tamb +55°C.
ATEX (Sira 18ATEX2287X )
II 1G, Ex ia IIC T4 Ga, −40°C Tamb +55°C
CE
European Conformity
30