Installation Guide
3 69-2122—05
EQUIPMENT SETTINGS
The Installer Menu is used to establish and modify the system’s equipment and option settings. These include equipment settings for boiler
operation, DHW management, zoning, auxiliary input/output operation, and option settings such as pump/valve exercise, and freeze protection.
Use Table 1 to record the equipment settings for this installation.
To record the equipment and option settings:
A Press the Home button to return to the Home Page display.
B Press and hold the OK button for 3 seconds until the message, INSTALLER MODE – ARE YOU SURE?, displays.
C Select YES, then press and release the OK button to display the Installer Menu.
D Select the Equipment Setup sub-menu.
E Record the configured settings in Table 1.
F Exit Installer mode by selecting the Installer Exit menu option.
Table 1. Installer Menu – Equipment Setup Sub-menu.
EQUIPMENT SETUP SUB-MENU
Sub-Menu and Option Range Factory Default Equipment Settings Used
BOILER SETTINGS
HIGH LIMIT 120°F to 225°F
(49°C to 107°C)
190°F
(88°C)
LOW LIMIT 60°F to 180°F (15°C to 82°C) 150°F
BOILER DIFF 2°F to 41°F (1°C to 23°C) /
AUTO
AUTO
W.W.S.D. - -
35°F to 100°F (2°C to 38°C)
70 °F
(21°C)
MIN. RETURN - - / 80°F to 180°F (27°C to 82°C) 140 °F
(60°C)
BOILER OPERATION
CYCLES/HOUR 2 to 6 4
FIRE DELAY 0 seconds to 3 minutes
(in 5 second increments)
10
(seconds)
PURGE TIME OFF, 10 seconds to
30 minutes
(in 10 second increments)
30
(seconds)
EXERCISE YES / NO YES
FREEZE PROT YES / NO YES
10V MOD. SELECT
10V MOD 0-10V / 2-10V 0-10V
USAGE NONE / BOILER NONE
DOMEST.HOT WATER
DHW ENABLE / DISABLE ENABLE
DHW PRIO YES / NO NO
PRIO.OVER. YES / NO YES
DHW DEVICE PUMP / VALVE PUMP
DHW VLV.OP 0 - 230 seconds
(in 5 second increments)
15
(seconds)
DHW PURGE YES / NO YES
DHW SENSOR YES / NO NO
DHW SETPOINT - -
60°F to 160°F (16°C to 71°C)
140°F
(60°C)
DHW DIFF - -
5°F to 40°F (2.5°C to 22°C)
20°F
(-7°C)
DHW VACANCY - -
[41°F + DHW DIFF] to 160°F
([5°C + DHW DIFF] to 71°C)
45°F
(7°C)
ZONING
HT DMND PRIO YES / NO NO
PRIO.OVER YES / NO NO
ZONING VALVES
TIME TO OPEN
5 - 230
(seconds)
15
(seconds)
HT DMND PRIO YES / NO NO