42 Installation Guidelines for 60 Hz Air-Cooled Generators
No transfer to
standby after utility
source failure.
MLCB (generator disconnect) is OFF (OPEN). Reset generator disconnect to ON (CLOSED).
Faulty transfer switch coil Contact an IASD for assistance
Faulty transfer relay. Contact an IASD for assistance
Transfer relay circuit open. Contact an IASD for assistance
Faulty control logic board. Contact an IASD for assistance
Engine may be warming up.
Refer to
Cold Smart Start.
Check the controller screen to verify status.
Unit consumes
large amounts of oil.
Excessive engine oil. Adjust oil to proper level.
Faulty engine breather. Contact an IASD for assistance
Improper type or viscosity of oil
See “Engine Oil Requirements” in the Owner’s
Manual.
Damaged gasket, seal, or hose. Check for oil leaks.
Restricted air filter. Replace air filter.
Wi-Fi network
connection broken
or intermittent
Various Refer to Wi-Fi module owner’s manual.
* Contact an IASD or visit www.honeywellgenerators.com/find-a-dealer for assistance.
Problem Cause Correction