Install Manual

Table Of Contents
Control Panel Start-Up/Testing
34 Installation Guidelines for 60 Hz Air-Cooled Generators
Setting The Exercise Timer
This generator is equipped with a configurable exercise
timer. There are two settings for the exercise timer:
Day/Time: The generator will start and exercise for
the period defined, on the day of the week and at
the time of day specified. During this exercise
period the unit runs for five minutes on all models,
and then shuts down.
Exercise frequency (how often the exercise will
take place): Can be set to Weekly, Biweekly, or
Monthly. If Monthly is selected, the day of the
month must be selected from 1–28. The generator
will exercise on that day each month. Transfer of
loads to the generator output does not occur during
the exercise cycle unless utility power is lost.
NOTE: If the installer tests the generator prior to
installation, press the ENTER button to skip setting up
the exercise timer.
NOTE: The exercise feature will operate only when the
generator is placed in the AUTO mode, and will not work
unless this procedure is performed. If Wi-Fi is not
enabled, the current date/time will need to be reset every
time power is removed from the controller via the
controller fuse and T1 circuit and/or battery connections.
NOTE: If Wi-Fi is enabled, the exercise timer will
automatically adjust for Daylight Savings Time
.
NOTE:
If using the Wi-Fi feature, the exercise time will be
set to a random weekday during daylight hours. This setting
can be changed later. Refer to the Wi-Fi manual for details.