Control Panel Start-Up/Testing
Installation Guidelines for 60 Hz Air-Cooled Generators 33
Cold Smart Start
The Cold Smart Start feature is enabled at the factory,
and can be disabled in the EDIT menu. The generator
will monitor ambient temperature and adjust its warm-up
delay accordingly when Cold Smart Start is enabled. If
the ambient temperature is below a fixed temperature
upon startup in AUTO mode (per the chart below), the
generator will warm up for 30 seconds, allowing the
engine to warm before the load is applied. If the ambient
temperature is at or above the fixed temperature, the
generator will start up with the normal warm-up delay of
six seconds. See the Cold Smart Start section of the
owner’s manual.
Use arrow keys to
scroll and find the first
number of your
activation code.
Press ENTER to
select.
Repeat this step until
all digits have been
entered.
Use ESCAPE to
correct previous digits.
What happens if “Wrong Passcode Try
Again” appears?
Re-enter the activation code. If a
second attempt is unsuccessful, check
the number against the code given on
activategen.com. If it is correct and the
generator will not accept it, contact 1-
888-9ACTIVATE (922-8482, US and
CA only).
Activation is complete
when all digits are
entered above and
your screen shows this
display.
Follow the controller
prompts to continue
setting the time
function. Refer to your
Owner’s Manual with
questions.
Table 7-1. Activation Chart
Display Reads Troubleshooting
Serial 123456789
Passcode XXXXX +/-
002230
Select Hour (0-23)
- 6 +
002231
Table 7-2. Cold Smart Start Set Points
Generator Size 9 kW–20 kW 22 kW
Fixed Temperature 50 °F (10 °C) 20 °F (-7 °C)