Install Manual

Table Of Contents
Electrical Connections
30 Installation Guidelines for 60 Hz Air-Cooled Generators
Battery Requirements
12 volts, Group 26R-540CCA minimum, or Group
35AGM-650CCA minimum.
NOTE: Do not use external battery chargers.
Battery Installation
(Group 26R batteries only): Fill the battery with
the proper electrolyte fluid if necessary.
Fully charge the battery before installing it.
Before installing and connecting the battery, complete the
following steps:
1. Verify generator is OFF.
2. Turn OFF utility power supply to the transfer
switch.
3. Remove 7.5A fuse from generator control panel.
Connecting Battery
See Figure 6-2. Battery cables (A, B) were factory
connected at the generator.
Figure 6-2. Battery Cable Connections
Connect cables to battery posts as follows:
1. Connect red battery cable (A: from starter
contactor) to positive battery post labeled POS or
(+). Tighten to 70 in-lbs (8 Nm).
2.
Connect black battery cable (B: from frame ground)
to negative battery post labeled NEG or (–). Tighten
to 70
in-lbs
(8 Nm).
3. Install red battery post cover (shipped with loose
parts).
NOTE: Apply dielectric grease to battery posts to
prevent corrosion.
NOTE: In areas where temperatures fall below 0°F
(-18°C), a pad type battery warmer is recommended to
aid in cold climate starting. The battery warmer is
available as part of a cold weather kit from any
Independent Authorized Service Dealer (IASD).
A battery warmer is not necessary for AGM-style
batteries.
Battery Disposal
Always recycle batteries in accordance with local laws
and regulations. Contact your local solid waste collection
site or recycling facility to obtain information on local
recycling processes. For more information on battery
recycling, visit the Battery Council International website
at: http://batterycouncil.org
(000137a)
WARNING
Explosion. Batteries emit explosive gases while charging.
Keep fire and spark away. Wear protective gear when
working with batteries. Failure to do so could result in
death or serious injury.
(000138a)
WARNING
+
001832
B
A
(000133)
WARNING
Explosion. Batteries emit explosive gases.
Always connect positive battery cable first to
avoid spark. Failure to do so could result in
death or serious injury.
WARNING
Environmental Hazard. Always recycle batteries at an
official recycling center in accordance with all local
laws and regulations. Failure to do so could result in
environmental damage, death or serious injury.