Install Manual
Table Of Contents
Fuel Conversion / Gas Connections
20 Installation Guidelines for 60 Hz Air-Cooled Generators
Fuel Consumption
Fuel Line Sizing
Selecting the correct size fuel line is crucial to the proper
operation of the unit.
IMPORTANT NOTE: The generator inlet size does
not dictate the size of gas pipe to be used!
For further information refer to NFPA 54 for NG, or NFPA
58 or ICC IFGC for LP.
Measure the distance from the generator to the gas
source.
IMPORTANT NOTE: The generator should be
plumbed directly from the source, not off the end of
an existing low pressure system.
Table 5-1. Fuel Consumption Chart
Generator
Natural Gas Propane
1/2 Load Full Load 1/2 Load Full Load
9 kW 2.55 / 90 3.40 / 120 0.87 / 3.29 / 32 1.37 / 5.20 / 50
11 kW 3.03 / 107 4.50 / 159 1.22 / 4.62 / 44 1.97 / 7.45 / 72
16 kW 6.17 / 218 8.75 / 309 2.03 / 7.70 / 74 2.94 / 11.11 / 107
20 kW 5.78 / 204 8.52 / 301 2.37 / 8.99 / 87 3.56 / 13.48 / 130
22 kW 6.46 / 228 9.26 / 327 2.53 / 9.57 / 92 3.90 / 14.77 / 142
* Natural gas is in m
3
/h / ft
3
/h
** Propane is in gal/h / L/h (LP) / ft
3
/h (LPV)
*** Values given are approximate
These are approximate values. Use the appropriate spec sheet or fuel data decal for specific values.
Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
NOTE: The gas supply and pipe MUST be sized at 100% load BTU/h (Megajoule/h) rating.
Always refer to the fuel data label for the proper BTU/h, Megajoule/h, and required gas pressures:
– Natural Gas:
BTU/h = ft
3
/h x 1000
Megajoules/h = m
3
/h x 37.26
– Liquid Propane Vapor:
BTU/h = ft
3
/h x 2500
Megajoules/h = m
3
/h x 93.15