16 Installation Guidelines for 60 Hz Air-Cooled Generators
Material Sufficient for Level Installation
See Figure 3-3. Prepare a rectangular area
approximately 5 in (127 mm) deep (A) and approximately
6 in (152 mm) longer and wider (B) than the footprint of
the generator. Verify the surface where the generator will
be mounted is compacted, leveled, and will not erode
over time. A concrete pad can be poured if desired or
required.
Figure 3-3. Compacted Soil or Gravel Pad
NOTE: If a concrete pad is required, follow all applicable
federal, state, or local codes.
Transportation Recommendations
Use a suitable cart or equipment to carry the generator,
including the wooden pallet, to the installation site. Place
cardboard between the cart and generator to prevent any
damage or scratches to the generator.
IMPORTANT NOTE: Do not lift, carry, or move the
generator by grasping the louvers. Doing so may
bend or damage the sheet metal.
Placement on Roofs, Platforms,
and Other Supporting Structures
Where required to place the generator on a roof,
platform, or other supporting structure, like a deck, the
generator shall be placed in accordance with the
requirements in NFPA 37, Section 4.1.3. The generator
can be located 18 in (457 mm) from structures having
combustible walls and 5 ft (1.52 m) from any operable
opening in the structure. The surface beneath the
generator and beyond shall be noncombustible to a
minimum distance of 12 in (30.5 cm). Consult with the
local Building Inspection Department or Fire Department
to determine which noncombustible materials are
approved for installation.