15kw Home Standby Generator Spec Sheet
3
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and
DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5
percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain points on the generator subject to change based
on installation parameters.
GENERATOR Model 006442-0 (11 kW) Model 006261-0 (15 kW) Model 006262-0 (20 kW)
Rated Maximum Continuous Power Capacity (LP) 11,000 Watts* 15,000 Watts* 20,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 10,000 Watts* 15,000 Watts* 18,000 Watts*
Rated Voltage 240 240 240
Rated Maximum Continuous Load Current – 240V (LP/NG) 45.8/41.7 62.5/62.5 83.3/75
Total Harmonic Distortion Less than 5% Less than 5% Less than 5%
Main Line Circuit Breaker 50 Amp 65 Amp 90 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 60Hz 60Hz 60Hz
Power Factor 1.0 1.0 1.0
Battery Requirement (not included) Group 26R, 12 Volts and 525 CCA Minimum
Unit Weight (Pounds/Kilos) 373/169.2 437/198.2 451/204.6
Dimensions (L x W x H) in./mm 48 x 25 x 29/1218 x 638 x 732
Sound output in dB(A) at 23 ft. (7m) with generator operating at normal
load 63 66 66
Sound output in dB(A) at 23 ft. (7m) with generator in WhisperCheck™
low speed exercise mode 57 60 60
ENGINE
Type of Engine GENERAC OHVI GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN
Number of Cylinders 2 2 2
Displacement 530cc 992cc 999cc
Cylinder Block Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc 12 Vdc
Oil Capacity Including Filter Approx. 1.7 Qts./1.6L Approx. 1.9 Qts./1.8L Approx. 1.9 Qts./1.8L
Operating RPM 3,600 3,600 3,600
Fuel Consumption
Natural Gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid Propane ft
3
/hr (gal/hr) [Liters/hr]
1/2 Load
Full Load
124 (3.51)
195 (5.52)
42.8 (1.18) [4.45]
70 (1.92) [7.28]
185 (5.24)
296 (8.38)
66.4 (1.83) [6.91]
104 (2.86) [10.82]
205 (5.8)
308 (8.72)
75.6 (2.08) [7.87]
140 (3.85) [14.57]
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet - 3.5-7” water column (7-13mm mercury) for natural gas, 10-12” water column
(19-22mm mercury) for LP gas. For Btu content, multiply ft
3
/hr x 2500 (LP) or ft
3
/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26
(NG).
CONTROLS
2-Line Plain Text Multi-Lingual LCD Display Simple user interface for ease of operation.
Mode Buttons: Auto Automatic Start on Utility failure. 7 day exerciser.
Manual Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Off Stops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance Messages Standard
Engine Run Hours Indication Standard
Programmable start delay between 2-1500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility Adjustable From 140-171V/190-216V
Future Set Capable Exerciser/Exercise Set Error Warning Standard
Run/Alarm/Maintenance Logs 50 Events Each
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC Warning Standard
Low Battery/Battery Problem Protection and Battery Condition Indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Under-Frequency/Overload/Stepper Overcurrent Protection Standard
Safety Fused/Fuse Problem Protection Standard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72Hz)/RPM Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring Protection Standard
Common External Fault Capability Standard
Field Upgradable Firmware Standard