User Guide

Table Of Contents
52 BACnet Commissioning Honeywell
15.5.2 Analog Value Object
Instance ID Object Name Description Units Present Value
Access Type
AV0
Frequency Setpoint Frequency Setpoint
Hz R
AV1
Output Frequency Output Frequency
Hz R
AV2
Motor Speed Motor Speed
Rpm R
AV3
Load (power) Motor Shaft Power
Percent R
AV4
Kilowatt Hours total
Megawatt Hour
Counter (Total)
kWh R
AV5
Motor Current Motor Current
Amps R
AV6
DC link Voltage DC link Voltage
Volts R
AV7
Motor Voltage Motor Voltage
Volts R
AV8
Unit Temperature
Heatsink Temperature
NOT IN NXL -series
° C
R
AV9
Motor Torque
In % of motor nominal
Torque
Percent R
AV10
Operating Days
Operating Days
(resettable)
Day R
AV11
Operating Hours
Operating Hours
(resettable)
Hour R
AV12
Kilowatt Hours
Kilowatt Hours
(resettable)
kWh R
AV13
Torque Reference
Torque Reference NOT
IN NXL -series
Percent R
AV14
Temperature Rise
Calculated motor
temperature 100,0% =
nominal temperature of
motor
NOT IN NXL -series
Percent R
AV15
FBProcessDataOut1 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV16
FBProcessDataOut2 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV17
FBProcessDataOut3 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV18
FBProcessDataOut4 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV19
FBProcessDataOut5 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV20
FBProcessDataOut6 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV21
FBProcessDataOut7 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV22
FBProcessDataOut8 Application specific
-32768.0 to +32767.0
resolution 1.0
R
AV23
Active Fault Code Active Fault Code -
R
AV24
Speed Reference
Speed Reference,
percentage of nominal
speed
Percent C
AV25
Current Limit Current Limit
Amps W
AV26
Min Frequency Minimum Frequency
Hz W
Continues on next page