User Guide
Table Of Contents
- 1. General
- 2. LonWorks C4 Option Board Technical Data
- 3. LonWorks Fieldbus C4 Option Board Layout and Connections
- 4. Installation of Honeywell NX LonWorks C4 Option Board
- 5. Commissioning
- 6. LonWorks Interface
- 7. Fault Tracking
- 8. Appendix 1
- 9. General Info
- 10. BACnet CJ Option Board Technical data
- 11. Bacnet Fieldbus CJ Option Board Layout and Connections
- 12. Grounding Cable Shield
- 13. Led Indications
- 14. Installation of Honeywell NX BACnet CJ Option Board
- 15. Commissioning
- 16. Fault Tracking
50 BACnet Commissioning Honeywell
15.5.1 Binary Value Object
Instance ID Object Name Description Inactive / Active Present Value
Access Type
BV0
Ready State Indicates whether the
drive is ready or not
Not Ready / Ready R
BV1
Run/Stop State Indicates whether the
drive is running or
stopped
Stop / Run R
BV2
Fwd/Rev State Indicates the rotation
direction of the motor
Fwd / Rev R
BV3
Fault State Indicates if a fault is
active
OK / Fault R
BV4
Warning State Indicates if a warning is
active
OK / Warning R
BV5
At Setpoint Ref. Frequency reached False / True R
BV6
At Zero Speed Motor Running at zero
speed
False / True R
BV7
General 0 Application specific bit
from drives General
Status Word
0 / 1 R
BV8
General 1 Application specific bit
from drives General
Status Word
0 / 1 R
BV9
General 2 Application specific bit
from drives General
Status Word
0 / 1 R
BV10
General 3 Application specific bit
from drives General
Status Word
0 / 1 R
BV11
General 4 Application specific bit
from drives General
Status Word
0 / 1 R
BV12
General 5 Application specific bit
from drives General
Status Word
0 / 1 R
BV13
General 6 Application specific bit
from drives General
Status Word
0 / 1 R
BV14
General 7 Application specific bit
from drives General
Status Word
0 / 1 R
BV15
Run/Stop CMD Command to start drive
(FB control is active)
Stop / Run C
BV16
Fwd/Rev CMD Command to change
rotational direction (FB
control is active)
Fwd / Rev C
BV17
Reset Fault Command to reset
Active Fault from dirve
0 / Reset C
BV18
FBFixedControlWord
Bit_3
Application Specific bit
From the Fixed Control
Word
0 / 1 C
BV19
FBFixedControlWord
Bit_4
Application Specific bit
From the Fixed Control
Word
0 / 1 C
BV20
FBFixedControlWord
Bit_5
Application Specific bit
From the Fixed Control
Word
0 / 1 C
BV21
FBFixedControlWord
Bit_6
Application Specific bit
From the Fixed Control
Word
0 / 1 C
BV22
FBFixedControlWord
Bit_7
Application Specific bit
From the Fixed Control
Word
0 / 1 C
Continues on next page