38 BACnet Grounding Cable Shield Honeywell
12.2 Grounding only one point on the net
In this manner of grounding, the shield is connected to ground only at the last device on the
net in the same way as described in chapter 12.1. Other devices of the net just pass the
shield.
We recommend you to use an Abico connector to fit the shields into the terminal.
1. Strip about 5 cm of the cable and cut off the grey cable shield. Remember to do
this for both bus cables (except for the last device).
2. Leave no more than 1 cm of the cable outside the terminal block and strip the data
cable at about 0.5 cm to fit in the terminals. See Figure 20.
Figure 20.
Note! Do this for both cables.
3. Fix both the cables on the frame with the clamp. See Figure 21.
Figure 21.
1 2 3 4 5
B
A
Shield