34 BACnet Technical Data Honeywell
10.1 System Software versions
OPT-CJ BACnet option board is supported from system software versions:
• NXL NXL00005V149.VCN
• NXS NXS00001V161.VCN
• NXP NXP00002V160.VCN
Autobaud detection and BACnet specific fault codes (readable from panel) are added from
system software versions:
• NXL NXL00005V248.VCN
• NXS NXS00001V163.VCN
• NXP NXP00002V162.VCN
Communication timeout is available from system SW versions. When not supported, the
default is 10 seconds.
• NXL NXL00005V254.VCN
• NXS NXS00001V167.VCN
• NXP NXP00002V168.VCN
OPT-CJ software version OPTCJ_10522V009 and newer:
New baud rate 76800 from software versions:
• NXL: NXL00005V257.VCN
• NXS: NXS00001V170.VCN
• NXP: NXP00002V171.VCN