Honeywell BACnet Technical Data 33
10. BACnet CJ Option Board Technical data
Interface OPT-CJ: Pluggable connector (5.08mm)
Data transfer
method
RS-485 MS/TP, half-duplex
Transfer cable Twisted pair (1 pair and shield)
Connections
Electrical
isolation
500 VDC
BACnet MS/TP As described in ANSI/ASHRAE Standards 135-
2004
Baud rate 9600, 19200, 38400 and 76800 baud (supports
autobaud detection)
Communications
MAC Addresses
1 to 127
Ambient
operating
temperature
–10°C…55°C
Storing
temperature
–40°C…60°C
Humidity <95%, no condensation allowed
Altitude Max. 1000 m
Environment
Vibration 0.5 G at 9…200 Hz
Safety
Fulfils EN50178 standard
Table 17. BACnet technical data