24 LonWorks Interface Honeywell
Field Description
object_id ID of object within node
invalid_id 1 means requested ID is not
implemented in this node
invalid_request
1 means request for
unimplemented function
disabled 1 means object disabled
electrical_fault
1 means drive is faultefd
in_alarm 1 means drive is in alarm
report_mask 1 means status is an event mask
Table 11.
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal
speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
nvoDrvRunHours
This output network variable provides the drive resettable operation time counter for the
motor in running hours. The maximum value for used SNVT is 65535 h. On the frequency
converter the value can go much higher. If the counter exceeds the SNVT’s maximum value,
the network variable stays at its maximum. In such cases the real value can be seen on
Honeywell NX’s operating keypad.