Honeywell LonWorks Interface 21
nviRstFault
This input network variable provides a fault reset. Setting value 1 for State and a non-zero
value for Value will reset an active fault in Honeywell NX. Default value is 0; 0.
State Value Command
0 any no action (0; 0)
1 0 no action (0; 1)
1 > 0 reset fault (200 ; 0)
-1
(0xFF)
any invalid (no action)
Table 7.
nviClrCntr
This input network variable provides a mechanism to clear the kWh trip counter or the Drive
total running hours trip counter.
1 MWh trip counter
2 Operation day trip counter
nviProcessIn1..8
These input network variables are sent directly to the application (see more detailed
explanation in chapter 6.5 Process Data) The valid range is 0 to 65535 (-163,840 to
163,835).
nviDigitalIn1..8
These input network variables are sent directly to the application (see more detailed
explanation in chapter 6.5 Process Data) Default value is 0; 0.
state value command
0 any off (0; 0)
1 0 off (0; 1)
1 > 0 on (200; 1)
-1
(0xFF)
any invalid (no action)
Table 8.
nviParCmd
This input network variable is used to read and write the parameters. The parameter
addresses are determined in the application. Every parameter and actual value has been
given an ID number in the application. The ID numbering of the parameter as well as the
parameter ranges and steps can be found in the application manual in question. The
parameter value must be given without decimals. Find the ID numbers of each
parameter/actual value in the application manual. The ID numbers are grouped as follows: