10 LonWorks Layout and Connections Honeywell
3.2.1 Grounding the bus cable shield directly to the frequency converter frame
using the RC-filter
1 Strip about 5 cm of the cable
as shown in the picture.
Figure 6.
2 Leave no more than 7 mm of the
data cable outside the terminal
block (Figure 7) and strip the
data cables at about 5 mm to fit
in the terminals (Figure 8).
Figure 7.
Continues on next page