Submittal Sheet

66-1121 G.R. 12-00 www.honeywell.com
201391, 32003167-001 SHAFT ADAPTERS FOR ML7999 CONTROLINKS™ ACTUATOR
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
3.
Rotate the valve shaft to match the actuator position.
4.
Partially tighten the hub setscrews to ensure the
actuator seats firmly against the mounting bracket with
the valve shaft centered in the actuator hub.
5.
Tighten the anti-rotation bolt to the torque
recommended for the selected bolt/nut combination.
6.
tighten the setscrews against the shaft to a torque of 60
lb.-in.
7.
Wire the actuator according to the instructions provided.
8.
Check the actuator operation by applying power and
running the actuator through at least one complete
cycle.
9.
If the operation is correct, turn on the gas supply to the
system.