Overview of Primary Product
V5011N TWO-WAY THREADED GLOBE VALVE
5 63-2548—3
Fig. 3. Close-off ratings at various control air pressures for V5011N Valves and MP953 Pneumatic Actuators. (continued)
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
IMPORTANT
1. Do not lift the valve by holding the stem.
2. Do not mount the valve with the stem pointed lower 
than horizontal.
3. Mount the valve with the flow arrow pointed in the 
direction of flow through the valve.
4. Mount the valve between aligned pipes. Mounting 
the valve on pipes that are not aligned causes 
leakage at the valve-to-pipe connection.
5. Ensure complete engagement on pipe to valve body 
threads.
6. Hold the valve body with a clamp or pipe wrench on 
the hexagonal fitting nearest the pipe to prevent 
damage to the valve body while mounting on the 
pipe. Refer to Fig. 4.
7. Be sure to allow enough room for installation and 
service. Clearance for valve installation is dependent 
on actuator size and the valve pipe size.
Location
Select a location where the valve, linkage, and actuator are 
within the appropriate pressure and temperature ratings.
Leave sufficient clearance above the valve to accommodate 
actuator installation and allow room for servicing the valve 
body. (Completely install the valve body in the pipe line before 
installing the actuator and linkage.)
When selecting a location for the valve, consider actuator 
mounting restrictions. Modutrol IV™ Motor crankshafts must 
be mounted horizontally.
M16054
SPRING RANGE PSI (kPa)
V5011N — 1/2 THROUGH 1-1/4 IN. REVERSE ACTING THREADED 
BODIES WITH 7 IN. REVERSE ACTING PNEUMATIC ACTUATOR
(NORMALLY OPEN)
4-11
(30-75)
3-7
(20-50)
8-13
(55-90)
7
(50)
14
(95)
17
(120)
18
 (125)
15
(105)
16
(110)
17
(120)
18
(125)
12
(85)
13
(90)
14
(95)
5
(35)
15
(105)
25
(170)
35
(240)
45
(310)
55
(380)
65
(450)
0
(0)
10
(70)
20
(140)
30
(205)
40
(275)
50
(345)
60
(415)
70
(48
0)
CLOSEOFF PRESSURE RATINGS PSI (kPa)
AIR PRESSURE IN ACTUATOR PSI (kPa)
1
16
(110)
12
(85)
13
(90)
15
(105)
11
(75)
14
 (95)
10
(70)
9
(60)
8
(55)
13
 (90)
12
 (85)
11
(75)
1 USE 4-11 PSI SPRING FOR POSITIONER MODEL (MP953E).
C
V
 .73 TO 2.9
C
V
 4.7
C
V
 7.3
C
V
 11.7
C
V
 18.7
M16053
S
PRING RANGE PSI (kPa)
V5011N — 1/2 THROUGH 1-1/4 IN. REVERSE ACTING 
THREADED BODIES WITH 8 IN. DIRECT ACTING  
PNEUMATIC ACTUATOR (NORMALLY CLOSED)
4-11
(30-75)
8-12
(55-85)
5
(35)
4
(30)
3
(20)
8
(55)
7
(50)
6
(40)
5
(35)
15
(105)
25
(170)
35
(240)
45
(310)
55
(380)
65
(450)
0
(0)
10
 (70)
20
(140)
30
(205)
40
(275)
50
(345)
60
(415)
70
(480)
CLOSEOFF PRESSURE RATINGS PSI (kPa)
0
(0)
1
 (10)
2
 (15)
3
 (20)
4
(30)
1
(10)
2
 (15)
USE 4-11 PSI SPRING FOR POSITIONER MODEL (MP953E).
1
1
C
V
 .73 TO 2.9
C
V
 4
.7
C
V
 7.3
C
V
 11.7
C
V
 18.7
AIR PRESSURE IN ACTUATOR PSI (kPa)