Installation Instructions

CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420 30
Connection to a CP-IO Bus Powered by the Separate Transformer
Fig. 21. Connection (L > 3 m) of RS485 interface 4 to a CP-IO Bus
NOTES:
N = max. 16 CP-EXPIO modules or 16 CP-DIO modules (or a mixture thereof). The mode switch of the inte-
grated termination resistor of the final CP-DIO (CP-DIO #N) must be set to “ON.” The CP-EXPIO module sup-
ports the addressing from address 0 to 15. Therefore, it supports 16 modules per channel. If the last module is
CP-EXPIO, the end of line resistor must be included.
For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7. For capacity restrictions, see “Connection to CP-IO Bus” section on
page 10. For fusing, see “Fusing” section on page 11.
CP-DIO/EXPIO #1
R
T
110VAC/230VAC
24VAC
F1
L > 3m
CP-DIO/EXPIO #N
24VAC
F2
110VAC/230VAC
FGND
485-
485+
N24 VAC
S24 VAC
FGND
24V0
24V~
FGND
FGND
485-
485+
N24 VAC
S24 VAC
FGND
R
T
TX
5V
GND
Isolaon
Barrier
RX
5V_ISO
-
+
GND_ISO
RS485-
RS485+
*
~
0
*
FGND
GND
CPO-PC400-W/CPO-PC400-UW