Installation Instructions

CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420 28
Connection to Modbus Modules
Fig. 19. Connection (L > 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a Modbus
NOTES:
N = max. 30 unit loads. Always power the CPO-PC400-W/CPO-PC400-UW and connected Modbus modules
with separate transformers. Termination resistors must be inserted directly into the terminals of the individual
Modbus modules.
Signal ground (signal reference) connection is recommended. For more information, see “General Information
on the RS485 Standard” section on page 7.
If the connected controllers do not have isolated RS485 interfaces and if they share a common ground between
the power supply and Earth ground, see the wiring diagram (Fig. 20) provided in Connection to Modbus devices
with non-isolated RS485 interfaces. This provides the best electrical noise rejection.
For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7.
Module #1
TX
5V
GND
Modbus
Isolaon
Barrier
RX
5V_ISO
GND_ISO
RS485+
RS485-
RT
110VAC/230VAC
24VAC
Modbus
Module #N
F1
RS485+
RS485-
Common
L > 3m
RT
Common
FGND
24V0
24V~
CH1+
CH1-
GND1
RS485+
RS485-
CPO-PC400-W/CPO-PC400-UW