Installation Instructions
Table Of Contents
CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420 22
Connection to BACnet MSTP Buses with Isolated Transceivers
Fig. 13. Connection (L > 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a BACnet Bus
NOTES:
— Always power the CPO-PC400-W/CPO-PC400-UW with a transformer separate to the connected BACnet MSTP
modules.
— N = max. 30 modules.
— Signal ground (signal reference) connection is recommended if not all devices are electrically isolated. For more
information, see “General Information on the RS485 Standard” section on page 7.
— If the connected controllers do not have isolated RS485 interfaces and if they share a common ground between
the power supply and Earth ground see the wiring diagrams (Fig. 14) provided in Recommended connection for
BACnet MSTP Buses with non-isolated RS485 interfaces. This provides the best electrical noise rejection.
— For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7. For fusing, see “Fusing” section on page 11.
— Termination resistors must be inserted directly into the terminals of the individual BACnet MSTP modules. In
the above figure, the CPO-PC400-W/CPO-PC400-UW is shown operating as the Master BACnet controller;
TX
5V
GND
CP-VAV/SPC #1
Isolaon
Barrier
RX
5V_ISO
GND_ISO
RS485+
RS485-
RT
110VAC/230VAC
24VAC
CP-VAV/SPC #N
F1
RS485+
RS485-
FGND
L > 3m
RT
RS485+
RS485-
FGND
CH1+
CH1-
GND1
24V~
24V0
FGND
CPO-PC400-W/CPO-PC400-UW