CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
EN0B-0085 IE10 R0420 22
Connection to BACnet MSTP Buses with Isolated Transceivers
Fig. 13. Connection (L > 3 m) of RS485 interfaces 1, 2, or 3 (RS485 interface 1 shown) to a BACnet Bus
NOTES:
Always power the CPO-PC400-W/CPO-PC400-UW with a transformer separate to the connected BACnet MSTP
modules.
N = max. 30 modules.
Signal ground (signal reference) connection is recommended if not all devices are electrically isolated. For more
information, see “General Information on the RS485 Standard” section on page 7.
If the connected controllers do not have isolated RS485 interfaces and if they share a common ground between
the power supply and Earth ground see the wiring diagrams (Fig. 14) provided in Recommended connection for
BACnet MSTP Buses with non-isolated RS485 interfaces. This provides the best electrical noise rejection.
For communication cable lengths, transmission speeds, and termination, see “General Information on the
RS485 Standard” section on page 7. For fusing, see “Fusing” section on page 11.
Termination resistors must be inserted directly into the terminals of the individual BACnet MSTP modules. In
the above figure, the CPO-PC400-W/CPO-PC400-UW is shown operating as the Master BACnet controller;