Brochure
88 63-8702
Motorized Zone Valves
VU54 Three-way Fan Coil Valves
70-6910 585
Commercial Components
Fan Coil Valves
VU54 Three-way Fan Coil Valves
Three-way fan coil zone valves are used to control hot or chilled
water in commercial HVAC equipment such as fan coil units,
terminal reheat coils and convectors.
• Compact construction for easy installation.
• Fits under the cover of most baseboard convectors with actuator
tted to valve body.
• VU54 provides three-way diverting control of water.
• 300 psi (2,000 kPa, PN20) operating pressure rating.
• Patented ball seal provides long service life, soft close off.
• Triple O-ring seal provides three lines of defense against corrosion
and water leakage around drive shaft.
• Quick opening ow curve.
• Choice of NPT end connections for iron or steel piping.
Dimensions in inches (millimeters)
2
2
1
1
VU53 VALVE WITH VU448 ACTUATOR
VU53 AND VU54 VALVE WITH ACTUATOR
VU5 ACTUATOR
2-3/8
(60)
7/8 DIA.
(22)
1-1/2
(38)
3-3/4
(133)
15/32
(12)
3/8
(10)
1-3/4
(44)
1-3/4
(44)
A
A
B
AB
7
3/8
(10)
A
2-1/8 (54)
(INVERTED
FLARE)
1-3/4
(44)
1-3/4
(44)
B
3-WAY
7/8 (22)
2-WAY
VALVE BODY SIZE A B
1/2 IN. SWEAT 1-5/6 (33) 1-5/6 (33)
3/4 IN. SWEAT 1-3/8 (35) 1-11/16 (43)
1 IN. SWEAT 1-11/16 (43) 1-11/16 (43)
1/2 IN. NPT 1-3/8 (35) 1-5/16 (33)
3/4 IN. NPT 1-11/16 (43) 1-7/16 (37)
1 IN. NPT 1-11/16 (43) 1-7/16 (37)
HEIGHT NEEDED TO REMOVE ACTUATOR OR COVER
OPENING FOR 1/2 IN. CONDUIT ON OPPOSITE SITE OF
MANUAL LEVER FOR ALL MODELS.
M18261A
Valve Type: Fan Coil Valve
Body Pattern: Three-way A-AB-B
Valve Action: Diverting
Connection Type: VU54N-Female NPT; VU54S-Sweat
Controlled Fluid: Chilled or hot water with up to 60% Glycol
Flow Characteristic: Quick Opening
Actuation: Must be purchased separately
Ambient Temperature Range: 34°F to 125°F at 200°F Fluid (1 to 52°C
@ 94°C Fluid)
Maximum Safe Operating Pressure (psi): 300 psig
Maximum Safe Operating Pressure (kPa): 2068 kPa
Materials (Body): Brass
Materials (Seat): Brass
Materials (Stem): Brass
Materials (Plug / Ball / Disc): Buna-N rubber
Materials (Packing): EPDM rubber
Approvals, CSA: CSA C/US
Used With: VU444 or VU844 Actuator
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (Cv) Capacity (Kv) Maximum Differential Pressure Ratings
(Close-off) (psi)
Maximum Differential Pressure Ratings
(Close-off) (kPa)
VU54N1007/U 1/2 in. DN15 4.0 Cv 3.4 Kv 20 psi 138 kPa
VU54N1015/U 3/4 in. DN20 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54N1023/U 1 in. DN25 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54N1031/U 3/4 in. DN20 4.0 Cv 3.4 Kv 20 psi 138 kPa
VU54N1049/U 3/4 in. DN20 5.0 Cv 4.3 Kv 15 psi 103 kPa
VU54S2008/U 1/2 in. DN15 4.0 Cv 3.4 Kv 20 psi 138 kPa
VU54S2016/U 3/4 in. DN20 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54S2024/U 1 in. DN25 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54S2057/U 3/4 in. DN20 5.0 Cv 4.3 Kv 15 psi 103 kPa
Material Number Pipe Size (inch) Pipe Size (DN) Capacity (Cv) Capacity (Kv) Maximum Differential Pressure Ratings
(Close-off) (psi)
Maximum Differential Pressure Ratings
(Close-off) (kPa)
VU54N1007/U 1/2 in. DN15 4.0 Cv 3.4 Kv 20 psi 138 kPa
VU54N1023/U 1 in. DN25 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54N1049/U 3/4 in. DN20 5.0 Cv 4.3 Kv 15 psi 103 kPa
VU54S2008/U 1/2 in. DN15 4.0 Cv 3.4 Kv 20 psi 138 kPa
VU54S2016/U 3/4 in. DN20 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54S2024/U 1 in. DN25 7.0 Cv 6.5 Kv 10 psi 69 kPa
VU54S2032/U 1/2 in. DN15 1.5 Cv 1.3 Kv 20 psi 138 kPa
VU54S2040/U 1/2 in. DN15 3.0 Cv 2.6 Kv 20 psi 138 kPa
VU54S2057/U 3/4 in. DN20 5.0 Cv 4.3 Kv 15 psi 103 kPa