Brochure
63-8702 83
Motorized Zone Valves
V4044 Line Voltage Diverting Valves
Flare Connection Sweat Connection
On-off and diverting line voltage valves consist of an actuator motor and
valve assembly for controlling the flow of hot or chilled water.
• Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• Motor may be replaced without removing the valve body or draining
the system.
• Suitable for heating and cooling applications.
Application: Hydronic Control
Valve Type: Zone Valve
Body Pattern: Three-way, Diverting
Valve Action: Spring Return to port A
Voltage: 120 Vac; Power Consumption – 9.6 VA
Frequency: 60 Hz
Actuation: Two position
De-energized Position: Port A Normally Closed
Electrical Connections: 18 in. leads (457 mm leads)
Ambient Temperature Range: 125°F Maximum (52°C Maximum)
Fluid Temperature: 40°F to 200°F (5°C to 93°C)
Static Pressure Rating (psi): 125 psi
Static Pressure Rating (kPa): 862 kPa
Materials (Body): Brass
Materials (Seat): Brass
Materials (Stem): Stainless Steel
Materials (Plug / Ball / Disc): Buna-N (NBR) Rubber Ball
Materials (Packing): EPDM rubber
Timing: Nominal Open – 30 sec
Operating Humidity Range (% RH): 5 to 95% relative humidity,
non-condensing.
Manual Opener: Yes
Approvals, Underwriters Laboratories Inc.: UL Component Listed: File
MH11826 Vol. 1
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water. Valve designed for cycling (not
constantly powered on) applications.
Current Draw: 0.08A
Dimensions in inches (millimeters). See page 73.
Material Number Capacity (Cv) Capacity (Kv) Pipe Size
(inch)
Pipe Size (DN) Connection
Type
Maximum Differential
Pressure Ratings (Close-
off) (psi)
Maximum Differential
Pressure Ratings (Close-
off) (kPa)
Changeover
Aquastat
V4044A1001/U 4 Cv 3.4 Kv 1/2 in. DN15 Flare 20 psi 138 kPa
V4044A1019/U 4 Cv 3.4 Kv 1/2 in. DN15 Sweat 20 psi 138 kPa
V4044A1191/U 7.0 Cv 6 Kv 3/4 in. DN20 Sweat 10 psi 69 kPa