82 63-8702
Motorized Zone Valves
V8043 Low Voltage Series 5000 QuickFit
®
Zone Valves for Canada
Flare Connection Inverted Flare
Dimensions in inches (millimeters)
AUTO
MAN OPEN
AB
HEIGHT NEEDED TO REMOVE
COVER.
DIMENSIONS FOR 1/2 IN.
COPPER TUBING.
DIMENSIONS FOR 3/4 IN COPPER TUBING.
DIMENSIONS FOR 1 IN. COPPER TUBING.
4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL BOARD ENCLOSURE.
V8043B VALVES THAT ARE NORMALLY OPEN IN THE DE-ENERGIZED
POSITION HAVE NO MANUAL LEVER. THE VALVES ALSO HAVE A
REVERSED POWERHEAD WHERE THE LEADWIRES EXIT THE
POWERHEAD ABOVE THE B (OUTLET) PORT RATHER THAN ABOVE
THE A (INLET) PORT.
OPENING FOR 1/2 IN. CONDUIT ON MANUAL LEVER SIDE FOR V8043
1
7
1
6
5
2
3
4
2
3
4
5
6
7
M23257
V8043 SWEAT QUICKFIT CONNECTION MODELS
2-3/8
(60)
7/8 DIA.
(22)
1-1/2
(38)
5-3/4
(146)
15/32
(12)
IN
OUT
3-1/2 (89)
1-3/4
(44)
3/8
(10)
1-3/4
(44)
1-9/16
(40)
1-3/4
(44)
3-1/8
(79)
3-1/2
(89)
1-7/8
(47)
3-11/16 (94)
®
Two-way on-off low voltage valves consist of an actuator and valve
assembly for controlling the flow of hot water.
All models may be installed without disassembling the valve.
Compact construction for easy installation.
Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
“Quick Fit” pushbutton powerhead makes it easy to remove for
service.
Series 5000 replacement powerhead is backward compatible with
series 1000 zone valves.
Innovative motor technology offers silent operation, water hammer
resist and longer life.
Application: Hydronic Control
Valve Type: Zone Valve
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to close
Voltage: 24 Vac; Power Consumption – 7.2 VA
Frequency: 50 Hz; 60 Hz
Capacity (Cv): 3.5 Cv
Capacity (Kv): 3 Kv
Actuation: Two position
De-energized Position: Normally Closed
Auxiliary End Switch: N.O. SPST
Ambient Temperature Range: 125°F Maximum (52°C Maximum)
Fluid Temperature: 50°F to 200°F (10°C to 93°C)
Maximum Differential Pressure Ratings (Close-off) (psi): 20 psi
Maximum Differential Pressure Ratings (Close-off) (kPa): 138 kPa
Static Pressure Rating (psi): 300 psi
Static Pressure Rating (kPa): 2068 kPa
Materials (Body): Brass
Materials (Seat): Brass
Materials (Stem): Stainless Steel
Materials (Plug / Ball / Disc): Buna-N (NBR) Rubber Ball
Materials (Packing): EPDM rubber
Timing: Nominal Open – 15 sec
Operating Humidity Range (% RH): 5 to 95% relative humidity,
non-condensing.
End Switch Rating: 50 VA pilot duty @ 24 V; 4.4 A running with 26.4 A
inrush @ 120 V
Manual Opener: Yes
Approvals, CSA: CSA Certified: File 1322
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water. Valve designed for cycling (not
constantly powered on) applications.
Current Draw: 0.32A
Material Number Pipe Size (inch) Pipe Size (DN) Connection Type Includes
V8043C5058/U 3/4 in. DN20 Sweat
V8043G5000/U 1/2 in. DN15 Sweat
V8043G5018/U 3/4 in. DN20 Sweat
V8043G5034/U 3/8 in. DN10 Flare With 2 straight 3/4 in. sweat adapters.
V8043G5125/U 1/2 in. DN15 Inverted Flare Less Adapters