Brochure

78 63-8702
Motorized Zone Valves
V8043 Low Voltage Normally Closed Zone Valves for Canada
Flare Connection Sweat Connection NPT Connection Sweat Connection with
terminal block
Inverted Flare
Two-way on-off low voltage valves consist of an actuator and valve
assembly for controlling the flow of hot water.
Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
All models may be installed without disassembling the valve.
Compact construction for easy installation.
Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
Actuator motor may be replaced without removing the valve body or
draining the system.
Application: Hydronic Control
Valve Type: Zone Valve
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to close
Voltage: 24 Vac; Power Consumption – 7.7 VA
Actuation: Two position
De-energized Position: Normally Closed
Electrical Connections: 18 in. (457 mm) leads (except for
V8043F1135/U which has screw terminals)
Ambient Temperature Range: 125°F Maximum (52°C Maximum)
Fluid Temperature: 50°F to 200°F (10°C to 93°C)
Materials (Body): Brass
Materials (Seat): Brass
Materials (Stem): Stainless Steel
Materials (Plug / Ball / Disc): Buna-N (NBR) Rubber Ball
Materials (Packing): EPDM rubber
Timing: Nominal Open – 15 sec
Operating Humidity Range (% RH): 5 to 95% relative humidity,
non-condensing.
Manual Opener: Yes
Approvals, Underwriters Laboratories Inc.: UL Listed: File MH11826
Approvals, CSA: CSA Certified: File 1322
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water. Valve designed for cycling (not
constantly powered on) applications.
Current Draw: 0.32A
Dimensions in inches (millimeters). See page 73.
Replacement Parts:
802360JA/U – 24V Replacement motor for V8043/44
802360UA/U – 24V, 50/60 Hz Replacement motor for steam and
heating Zone Valves
Material
Number
Pipe
Size
(inch)
Pipe
Size
(DN)
Connection
Type
Frequency Capacity
(Cv)
Capacity
(Kv)
Auxiliary
End
Switch
Maximum Differential
Pressure Ratings
Closeoff (psi [kPa])
Static Pressure
Rating (psi [kPa])
End Switch
Rating
Includes
V8043C1033/U 3/8 in. DN10 Flare 50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 125 psi (862 kPa) With 2 straight
3/4 in. sweat
adapters.
V8043C1058/U 3/4 in. DN20 Sweat 50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 125 psi (862 kPa)
V8043C1066/U 1 in. DN25 Sweat 50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 125 psi (862 kPa)
V8043C1116/U 3/8 in. DN10 Flare 50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 125 psi (862 kPa) Less Adapters
V8043C1124/U 1/2 in. DN15 Inverted
Flare
50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 125 psi (862 kPa) Less Adapters
V8043C3302/U 3/8 in. DN10 Flare 50 Hz;
60 Hz
3.5 Cv 3 Kv 20 psi (138 kPa) 300 psi (2068 kPa) With 2 straight
3/4 in. sweat
adapters.
V8043C3310/U 1/2 in. DN15 Inverted
Flare
60 Hz 3.5 Cv 3 Kv 20 psi (138 kPa) 300 psi (2068 kPa) Less Adapters
V8043D3300/U 3/8 in. DN10 Flare 50 Hz;
60 Hz
3.5 Cv 3 Kv 300 psi (2068 kPa) With 2 straight
3/4 in. sweat
adapters.
V8043D3318/U 1/2 in. DN15 Inverted
Flare
60 Hz 3.5 Cv 3 Kv 300 psi (2068 kPa)
V8043F1135/U 3/4 in. DN20 Sweat 50 Hz;
60 Hz
3.5 Cv 3 Kv N.O. SPST 20 psi (138 kPa) 125 psi (862 kPa) 50 VA pilot duty
@ 24 V; 4.4 A
running with
26.4 A inrush @
120 V
End Switch
enclosure.
V8043G1000/U 1/2 in. DN15 Sweat 50 Hz;
60
Hz
3.5 Cv 3 Kv N.O. SPST 20 psi (138 kPa) 125 psi (862 kPa) 50 VA pilot duty
@ 24 V; 4.4 A
running with
26.4 A inrush @
120 V