Brochure
64 63-8702
Aquastat
®
Controllers
R8182 Combination Protectorelay
®
and Hydronic Heating Controllers
Immersion type Aquastat
®
controller and oil burner primary control
provides high limit and low limit/circulator control for oil-fired
hydronic heating systems.
• Use in intermittent ignition applications.
• Capable of zone control with zone valves.
• Circulator zone control with ZC and ZR terminals on R8182D,E,H,J.
• Flame failure during the running cycle results in a 45 second
attempt to restart.
• If unsuccessful, safety shutoff occurs, requiring manual reset
before burner can be restarted.
• R8182D,E,F mount directly on burner; R8182H,J mount on 4 x 4 in.
junction box and include 5 ft (1.5 m) armored capillary with remote
sensor.
• C554A Cadmium Sulfide Flame Detector and a 24 Vac thermostat
required.
• Auxiliary ZC and ZR terminals may be used to provide circulator
zone control through an R845A Switching Relay.
Voltage: 120 Vac
Power Consumption: 9 W
Frequency: 60 Hz
Temperature Range: Maximum – 250°F (121°C) at element
Operating Temperature Range:
High Limit – 130°F to 240°F (54°C to 116°C);
Low Limit – 110°F to 220°F (43°C to 104°C)
Anticipator Setting: 0.2 A
Maximum Safe Operating Pressure (psi): 200 psi on immersion well;
100 psi direct immersion.
Maximum Safe Operating Pressure (kPa): 1378 kPa on immersion
well; 90 kPa direct immersion.
Electrical Ratings, Ignition: 360 VA
Electrical Ratings, Burner:
At Full Load – 4.4 A @ 120 Vac;
At Locked Rotor – 26.4 A @ 120 Vac
Timing: Safety Switch – 45 sec
Dimensions: 7 1/8 in. high x 5 1/4 in. wide x 3 7/16 in. deep. (181 mm
high x 133 mm wide x 87 mm deep.)
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Approvals, Underwriters Laboratories Inc.: UL Listed: File No. listed:
MP268, Vol. 3,4 (R8182D,E,F), Vol. 37 (R8182H,J), Sec. 1.
Approvals, CSA: File No. 095329
Material Number Differential Temperature Mounting Insulation Depth Includes
R8182D1079/U High limit: 10°F fixed; Low limit/circulator: 10°F to 25°F adj. Vertical Mount 1 1/2 in. (38 mm) Stop dial; Heat Conductive Compound
R8182D1111/U High limit: 10°F fixed; Low limit/circulator: 10°F to 25°F adj. Horizontal 1 1/2 in. (38 mm) Stop dial; Heat Conductive Compound
R8182H1070/U High limit: 10°F fixed; Low limit/circulator: 10°F to 25°F adj. Junction box mount 1 1/2 in. (38 mm) Stop dial; Heat Conductive Compound
Dimensions in inches (millimeters)
M4517
1 VERTICAL MOUNT SHOWN.
1
5-1/4 (133)
3-1/4 (83)
7-1/8
(181)
3-9/16
(91)
3/16
(5)
1-5/16
(33)
2-7/16
(62)
KNOCKOUTS
FOR 1/2 IN.
(13 MM)
CONDUIT (5)
VERTICAL
MOUNT
ONLY
HORIZONTIAL
MOUNT ONLY
M4518
1 SIDE MOUNTED HINGE SHOWN.
1
5-1/4 (133)
3-7/16 (87)
7-1/8
(181)
3-7/16
(87)
1/2 (13)
3-3/8 (86)
7/8
(22)
KNOCKOUTS
FOR 1/2 IN. (13 MM)
CONDUIT (5)