Brochure

58 63-8702
Aquastat
®
Controllers
L8124 Triple Aquastat
®
Relay
Immersion-type controllers that combine high limit protection with
low limit and circulator control in forced hydronic heating systems,
including domestic hot water service.
Provide multizone control by using a separate circulator and R845
Relay for each zone.
Include diaphragm powerhead and Micro Switch™ assembly that
respond to temperature changes in boiler water.
Mount directly to boiler.
Select models include large transformers and extra terminals for
supplying power to low voltage zone valves.
Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus
current draw of gas valve on L8124E).
Differential Temperature: High limit: 10°F fixed; low limit: 10-25°F adj.
Frequency: 60 Hz
Electrical Connections: Quick Connect/Screw
Switching Action: SPST: High Limit
SPDT: Low Limit and Circulator Control
Maximum Safe Operating Pressure (psi): 200 psi on outside of
immersion well, 100 psi on capsule if inserted directly.
Maximum Safe Operating Pressure (kPa): 1378 kPa on outside of
immersion well, 690 kPa on capsule if inserted directly.
Electrical Ratings, Circulator:
At Full Load – 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; 
At Locked Rotor – 44.4 A @ 120 Vac: 22.2 A @ 240 Vac
Electrical Ratings, Burner:
At Full Load – 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; 
At Locked Rotor – 44.4 A @ 120 Vac: 22.2 A @ 240 Vac
Operating Humidity Range (% RH): 0 to 95% RH, non-condensing
Operating Temperature Range:
High Limit – 130°F to 240°F (54°C to 116°C) adjustable;
Low Limit – 110°F to 220°F (43°C to 104°C) adjustable
Temperature Range: Maximum Ambient temp case: 150°F (66°C);
Maximum Sensing element 265°F (129°C)
Approvals, Underwriters Laboratories Inc.: UL Listed (models with
well): File No. MP466, Guide No. MBPR; UL Component Recognized
(models without well): File No. MP466, Guide No. MBPR2
Approvals, CSA: File No. 095329
Material Number Application Burner Control Voltage
Insulation Depth
Mounting
L8124A1007/U High Limit Protection, Low Limit and Circulation Control 120 Vac; 60 Hz 1 1/2 in. (38 mm) Vertical Mount
L8124A1015/U High Limit Protection, Low Limit and Circulation Control 120 Vac; 60 Hz 3 in. (76 mm) Vertical Mount
L8124C1003/U Triple Aquastat Relay with High limit 120 Vac; 60 Hz 1-1/2 in (38 mm) Horizontal
L8124E1016/U Triple Aquastat Relay with High limit 120 Vac; 60 Hz Vertical Mount
L8124G1020/U Triple Aquastat Relay with High limit 120 Vac; 60 Hz Vertical Mount
L8124L1011/U Triple Aquastat Relay with High limit 120 Vac; 60 Hz Horizontal