50 63-8702
Aquastat
®
Controllers
L4006; L6006 Aquastat
®
Controller
Aquastat
®
Controllers are immersion type devices for limiting or
regulating the temperature of liquids in boilers, storage tanks, and
other applications where temperature control is required.
Totally enclosed Micro Switch™ snap-acting switches operate on
temperature rise to setpoint.
Visible control point scale and external adjustment screw permit
easy setting.
Horizontal or vertical insertion of the sensing element.
Direct or well immersion of the sensing element.
Models available for strap-on mounting.
Remote bulb model may be used to sense air temperature in ducts
and in outside air sensing applications.
Select models have wells.
UL limit rated device.
Temperature Range: Maximum – 150°F (Maximum – 66°C)
Bulb Size: 3/8 in. x 2 7/8 in. copper (10 mm x 73 mm copper)
Electrical Ratings:
At Full Load – 8 A @ 120 Vac: 5.1 A @ 240 Vac;
At Locked Rotor – 48 A @ 120 Vac: 30.6 A @ 240 Vac
Millivolt – 0.25 A @ 0.25 to 12 Vdc
Dimensions: Case – 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep (Case –
143 mm high x 51 mm wide x 54 mm deep)
Approvals, Underwriters Laboratories Inc.: UL Component Recognized:
File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
Approvals, CSA: File No. 095329
M8957A
KNOCKOUT FOR 3/4 (19 )
CONDUIT ON ALL MODELS. SIMILAR
KNOCKOUT ON BOTTOM FOR
HORIZONTAL INSERTION AND
REMOTE BULB MODELS.
1 (25)
5/16
(8)
2 (51)
2-1/8 (54)
5-5/8
(136)
1-7/8
(48)
3/16
(5)
RESET
BUTTON
(L4006E,
L4008E
ONLY)
KNOCKOUT FOR 3/4 (19)
CONDUIT ON VERTICAL
INSERTION MODELS ONLY
ELEMENT FOR HORIZONTAL IMMERSION
3/4
(19)
ELEMENT
FOR VERTICAL
IMMERSION
11/16
(18)
3/4
(19)
Material Number Application Switching Action Operating
Temperature
Range
Differential
Temperature
Well Spud Size Capillary Length Mounting Includes
L4006A1009/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
1/2 in. NPT
(13 mm NPT)
1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A
L4006A1017/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
1/2 in. NPT
(13 mm NPT)
1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A
L4006A1132/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
3/4 in. NPT
(19 mm NPT)
3 in. (76 mm) Horizontal or
Vertical
Stop factory-set at
160°F (71°C); 3/4 in.
well - 123871A
L4006A1678/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
3 in. (76 mm) Horizontal or
Vertical
Stop factory-set at
240°F (116°C); Heat-
conductive compound
L4006A1959/U High or Low limit SPST, contacts break
on temperature rise.
40°F to 180°F
(4°C to 82°C)
5°F Fixed
(3°C fixed)
3 in. (76 mm) Horizontal or
Vertical
Heat-conductive
compound
L4006A1967/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
1/2 in. (13 mm) 1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A;
Stop factory-set at
240°F (116°C)
L4006A2007/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
3 in. (76 mm) Horizontal
L4006B1007/U Circulator SPST, contacts make
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
1/2 in. (13 mm) 1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A