Brochure
50 63-8702
Aquastat
®
Controllers
L4006; L6006 Aquastat
®
Controller
Aquastat
®
Controllers are immersion type devices for limiting or
regulating the temperature of liquids in boilers, storage tanks, and
other applications where temperature control is required.
• Totally enclosed Micro Switch™ snap-acting switches operate on
temperature rise to setpoint.
• Visible control point scale and external adjustment screw permit
easy setting.
• Horizontal or vertical insertion of the sensing element.
• Direct or well immersion of the sensing element.
• Models available for strap-on mounting.
• Remote bulb model may be used to sense air temperature in ducts
and in outside air sensing applications.
• Select models have wells.
• UL limit rated device.
Temperature Range: Maximum – 150°F (Maximum – 66°C)
Bulb Size: 3/8 in. x 2 7/8 in. copper (10 mm x 73 mm copper)
Electrical Ratings:
At Full Load – 8 A @ 120 Vac: 5.1 A @ 240 Vac;
At Locked Rotor – 48 A @ 120 Vac: 30.6 A @ 240 Vac
Millivolt – 0.25 A @ 0.25 to 12 Vdc
Dimensions: Case – 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep (Case –
143 mm high x 51 mm wide x 54 mm deep)
Approvals, Underwriters Laboratories Inc.: UL Component Recognized:
File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
Approvals, CSA: File No. 095329
M8957A
KNOCKOUT FOR 3/4 (19 )
CONDUIT ON ALL MODELS. SIMILAR
KNOCKOUT ON BOTTOM FOR
HORIZONTAL INSERTION AND
REMOTE BULB MODELS.
1 (25)
5/16
(8)
2 (51)
2-1/8 (54)
5-5/8
(136)
1-7/8
(48)
3/16
(5)
RESET
BUTTON
(L4006E,
L4008E
ONLY)
KNOCKOUT FOR 3/4 (19)
CONDUIT ON VERTICAL
INSERTION MODELS ONLY
ELEMENT FOR HORIZONTAL IMMERSION
3/4
(19)
ELEMENT
FOR VERTICAL
IMMERSION
11/16
(18)
3/4
(19)
Material Number Application Switching Action Operating
Temperature
Range
Differential
Temperature
Well Spud Size Capillary Length Mounting Includes
L4006A1009/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
1/2 in. NPT
(13 mm NPT)
1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A
L4006A1017/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
1/2 in. NPT
(13 mm NPT)
1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A
L4006A1132/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
3/4 in. NPT
(19 mm NPT)
3 in. (76 mm) Horizontal or
Vertical
Stop factory-set at
160°F (71°C); 3/4 in.
well - 123871A
L4006A1678/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
– 3 in. (76 mm) Horizontal or
Vertical
Stop factory-set at
240°F (116°C); Heat-
conductive compound
L4006A1959/U High or Low limit SPST, contacts break
on temperature rise.
40°F to 180°F
(4°C to 82°C)
5°F Fixed
(3°C fixed)
– 3 in. (76 mm) Horizontal or
Vertical
Heat-conductive
compound
L4006A1967/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
1/2 in. (13 mm) 1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A;
Stop factory-set at
240°F (116°C)
L4006A2007/U High or Low limit SPST, contacts break
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F to 30°F
adj. (3°C to
17°C adj.)
– 3 in. (76 mm) Horizontal –
L4006B1007/U Circulator SPST, contacts make
on temperature rise.
100°F to 240°F
(38°C to 116°C)
5°F Fixed
(3°C fixed)
1/2 in. (13 mm) 1 1/2 in.
(38 mm)
Horizontal or
Vertical
1/2 in. well - 123869A