Brochure

48 63-8702
Temperature Controllers
T775 Series 2000 Special Stand-Alone Controllers
T775 electronic remote temperature controller, is the next generation
in commercial/agricultural control - capable of remote sensing
temperature, humidity, pressure, etc., and providing switched and/or
proportional outputs to various types of loads.
Universal model (T775U) can control pressure, humidity, or any
variable analog input.
Special boiler model (T775P) for boiler control.
Special Staged Sequencing Model (T775L) for sequence staging of
relays with one or two setpoints.
Special Expansion Model (T775S) for staging up to 12 relays with
two setpoints (each T775S provides 4 relays).
Save time on installations with the easy-to-use graphical Interface,
large display, and the intuitive programming.
Use the time clock scheduler or digital input to control the setback
and disable output options to help save energy.
Provide very fast or very fast response times on modulating outputs
by adjusting the integral and derivative times (PI or PID).
Configure models with reset in a few easy steps.
Eliminate the need for a separate time delay device and protect
equipment with the minimum off time option.
Use the T775L and T775P to stage up to 12 relays (with optional
T775S) from two independent heat or cool setpoints.
Support for digital output alarm on the T775P configurable based
on minimum, maximum, or differential temperature.
Analog Output: 4-20 mA; 0-10 Vdc; 2-10 Vdc; Electronic Series 90
Voltage: 24 Vac or 120/240 Vac
Frequency: 50 Hz; 60 Hz
Relay Contact Ratings: 24 Vac – 10.0A resistive; 120 Vac – 1/2 hp;
9.8 AFL, 58.8 ALR, 125 VA Pilot Duty; 240 Vac – 1/2 hp; 4.9 AFL,
29.4 ALR, 125 VA Pilot Duty
Approximate, Dimensions: 8 5/32 in. high x 4 13/32 in. wide x
215/16 in. deep (207.1 mm high x 112.1 mm wide x 74 mm deep)
Sensor Element: 1097 ohms PTC at 77°F (25°C)
Setpoint Temperature Range: -40°F to 248°F (-40°C to 120°C)
Operating Temperature Range: Ambient – -40°F to 125°F @ 50 Hz;
-40°F to 140°F @ 60 Hz (Ambient – -40°C to 52°C @ 50 Hz; -40°C to
60°C @ 60 Hz)
Accuracy: ±1°F at 77°F (±1°C at 25°C)
Throttling Range: 1°F to 150°F (0.5°C to 66°C)
Differential Temperature: 1°F to 150°F (0.5°C to 66°C)
Expandable: T775L or T775P - Add 1 or 2 T775Ss (4 relays ea)
Replaces: T775U2006/U can be used to replace H775A1006;
H775A1022; H775A1048; H775A1063; H775B1005; H775C1004;
H775D1003; or H775E1002
Approvals, Canadian Underwriters Laboratories Inc.: Approved
Approvals, Underwriters Laboratories Inc.: Approved
Approvals, Others: IP65: Approved
Approvals, CE: Approved
Approvals, C-Tick: Approved
Accessories:
107324A/U – Capillary Holder Assembly, 8 3/8 in. long
H7655A1001/U – Wall Humidity Sensor, 5% RH, 0-10 Vdc fixed output
H7655B2014/U – Duct Humidity Sensor, 5% RH, Selectable 4-20mA or
0-5/10Vdc, with 20K ohm temp
P7640A1000/U – Panel Differential Pressure Transmitter, 0-.1",
0-.25", 0-.5", 0-1" Selectable
P7640A1018/U – Panel Differential Pressure Transmitter, 0-.1",
0-.25", 0-.5", 0-1" Selectable
P7640A1026/U – Panel Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640A1034/U – Panel Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640B1008/U – Duct Differential Pressure Transmitter,0-.1", 0-.25",
0-.5", 0-1" Selectable
P7640B1016/U – Duct Differential Pressure Transmitter, 0-.1", 0-.25",
0-.5", 0-1" Selectable
P7640B1024/U – Duct Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640B1032/U – Duct Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
Material
Number
Application Type Stages
Loop
Control
Output Bulb Size Relay
Outputs
Sensor Included Digital Output
Alarm Ratings
Sensor Inputs
T775L2007/U Sequence staging
of relays with one
or two setpoints
Stage Sequencer
with Reset Option-
NEMA 1
Yes relay
w/ RESET
1/4 in. diameter x
2 in. long (6.35 mm
diameter x 50.8 mm)
4 SPDT 50021579-001 (1) 2 (max distance
1,000 ft [304 m])
T775P2003/U Boiler Control Special Boiler with
Reset-NEMA 1
Yes relay
w/ RESET
1/4 in. diameter x
2 in. long (6.35 mm
diameter x 50.8 mm)
4 SPDT 50021579-001 (3) AC – 30 Vac RMS;
1.5 A steady 3A
inrush P.F. 0.45
N.C.; 20 Vac RMS;
100 mA minimum
load on N.O. and
N.C. contacts, DC –
1 mA at 100 mV DC
minimum load
3 (max distance
1,000 ft [304 m])
T775S2008/U Staging up to 12
relays with two
setpoints
Relay Expansion
Module-NEMA 1
4 SPDT None
T775U2006/U Control pressure,
humidity, or any
medium with an
analog input
Universal -
Humidity, Pressure,
etc.-NEMA 1
relay
w/ RESET
2 SPDT None 2 (Sensor B used
for reset only)
(max distance
1,000 ft [304 m])
T775U2016/U Control pressure,
humidity, or any
medium with an
analog input
Universal -
Humidity, Pressure,
etc.-NEMA 1
relay
w/ RESET
2 SPDT None 2 (Control
to Sensor A
(Universal Input)
or Sensor B (temp)
Independently)
(max distance
1,000 ft [304 m])