Temperature Controllers
T775 Series 2000 Special Stand-Alone Controllers
T775 electronic remote temperature controller, is the next generation
in commercial/agricultural control - capable of remote sensing
temperature, humidity, pressure, etc., and providing switched and/or
proportional outputs to various types of loads.
• Universal model (T775U) can control pressure, humidity, or any
variable analog input.
• Special boiler model (T775P) for boiler control.
• Special Staged Sequencing Model (T775L) for sequence staging of
relays with one or two setpoints.
• Special Expansion Model (T775S) for staging up to 12 relays with
two setpoints (each T775S provides 4 relays).
• Save time on installations with the easy-to-use graphical Interface,
large display, and the intuitive programming.
• Use the time clock scheduler or digital input to control the setback
and disable output options to help save energy.
• Provide very fast or very fast response times on modulating outputs
by adjusting the integral and derivative times (PI or PID).
• Configure models with reset in a few easy steps.
• Eliminate the need for a separate time delay device and protect
equipment with the minimum off time option.
• Use the T775L and T775P to stage up to 12 relays (with optional
T775S) from two independent heat or cool setpoints.
• Support for digital output alarm on the T775P configurable based
on minimum, maximum, or differential temperature.
Analog Output: 4-20 mA; 0-10 Vdc; 2-10 Vdc; Electronic Series 90
Voltage: 24 Vac or 120/240 Vac
Frequency: 50 Hz; 60 Hz
Relay Contact Ratings: 24 Vac – 10.0A resistive; 120 Vac – 1/2 hp;
9.8 AFL, 58.8 ALR, 125 VA Pilot Duty; 240 Vac – 1/2 hp; 4.9 AFL,
29.4 ALR, 125 VA Pilot Duty
Approximate, Dimensions: 8 5/32 in. high x 4 13/32 in. wide x
215/16 in. deep (207.1 mm high x 112.1 mm wide x 74 mm deep)
Sensor Element: 1097 ohms PTC at 77°F (25°C)
Setpoint Temperature Range: -40°F to 248°F (-40°C to 120°C)
Operating Temperature Range: Ambient – -40°F to 125°F @ 50 Hz;
-40°F to 140°F @ 60 Hz (Ambient – -40°C to 52°C @ 50 Hz; -40°C to
60°C @ 60 Hz)
Accuracy: ±1°F at 77°F (±1°C at 25°C)
Throttling Range: 1°F to 150°F (0.5°C to 66°C)
Differential Temperature: 1°F to 150°F (0.5°C to 66°C)
Expandable: T775L or T775P - Add 1 or 2 T775Ss (4 relays ea)
Replaces: T775U2006/U can be used to replace H775A1006;
H775A1022; H775A1048; H775A1063; H775B1005; H775C1004;
H775D1003; or H775E1002
Approvals, Canadian Underwriters Laboratories Inc.: Approved
Approvals, Underwriters Laboratories Inc.: Approved
Approvals, Others: IP65: Approved
Approvals, CE: Approved
Approvals, C-Tick: Approved
Accessories:
107324A/U – Capillary Holder Assembly, 8 3/8 in. long
H7655A1001/U – Wall Humidity Sensor, 5% RH, 0-10 Vdc fixed output
H7655B2014/U – Duct Humidity Sensor, 5% RH, Selectable 4-20mA or
0-5/10Vdc, with 20K ohm temp
P7640A1000/U – Panel Differential Pressure Transmitter, 0-.1",
0-.25", 0-.5", 0-1" Selectable
P7640A1018/U – Panel Differential Pressure Transmitter, 0-.1",
0-.25", 0-.5", 0-1" Selectable
P7640A1026/U – Panel Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640A1034/U – Panel Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640B1008/U – Duct Differential Pressure Transmitter,0-.1", 0-.25",
0-.5", 0-1" Selectable
P7640B1016/U – Duct Differential Pressure Transmitter, 0-.1", 0-.25",
0-.5", 0-1" Selectable
P7640B1024/U – Duct Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
P7640B1032/U – Duct Differential Pressure Transmitter, 0-1", 0-2.5",
0-5", 0-10" Selectable
Material
Number
Application Type Stages
Loop
Control
Output Bulb Size Relay
Outputs
Sensor Included Digital Output
Alarm Ratings
Sensor Inputs
T775L2007/U Sequence staging
of relays with one
or two setpoints
Stage Sequencer
with Reset Option-
NEMA 1
Yes relay
w/ RESET
1/4 in. diameter x
2 in. long (6.35 mm
diameter x 50.8 mm)
4 SPDT 50021579-001 (1) 2 (max distance
1,000 ft [304 m])
T775P2003/U Boiler Control Special Boiler with
Reset-NEMA 1
Yes relay
w/ RESET
1/4 in. diameter x
2 in. long (6.35 mm
diameter x 50.8 mm)
4 SPDT 50021579-001 (3) AC – 30 Vac RMS;
1.5 A steady 3A
inrush P.F. 0.45
N.C.; 20 Vac RMS;
100 mA minimum
load on N.O. and
N.C. contacts, DC –
1 mA at 100 mV DC
minimum load
3 (max distance
1,000 ft [304 m])
T775S2008/U Staging up to 12
relays with two
setpoints
Relay Expansion
Module-NEMA 1
4 SPDT None
T775U2006/U Control pressure,
humidity, or any
medium with an
analog input
Universal -
Humidity, Pressure,
etc.-NEMA 1
relay
w/ RESET
2 SPDT None 2 (Sensor B used
for reset only)
(max distance
1,000 ft [304 m])
T775U2016/U Control pressure,
humidity, or any
medium with an
analog input
Universal -
Humidity, Pressure,
etc.-NEMA 1
relay
w/ RESET
2 SPDT None 2 (Control
to Sensor A
(Universal Input)
or Sensor B (temp)
Independently)
(max distance