Brochure

42 63-8702
R847 Heavy Duty Relay
Designed for control of relatively heavy duty 120 or 240 Vac electrical
loads such as cooling compressors.
Internal, flexible leads permit SPST or DPST switching.
Application: Enclosed heavy duty DPST or SPST switching relay for 24
volt 2-wire thermostat control of high-current loads such as cooling
compressors. 120 volt primary power supply.
Electrical Connections: Main- 2-Wire; Control Circuit- 2-Wire
Coil Ratings Voltage: 24 Vac; Maximum Pull-in Voltage-2.0 A
Coil Ratings: 8.4 VA (Sealed); 21.4 VA (inrush)
Coil Ratings Current: 0.4A
Contact Ratings (AFL): 22A @ 120 Vac: 10A @ 240 Vac
Contact Ratings (ALR): 120 Vac – 100A; 240 Vac – 50A
Approximate, Dimensions: 5 1/4 in. high x 4 1/4 in. wide x 2 3/4 in.
deep (133 mm high x 108 mm wide x 70 mm deep)
Approvals, CSA: Certified: File No. LR1620
Approvals, Underwriters Laboratories Inc.: Listed: File No. SA481,
Guide No. SDF4
Tradeline Value: Tradeline
R847A wired to break one side of the circuit with SPST switching.
M16562
POWER
SUPPLY
MOVE
FLEXIBLE
LEAD
TO L1
THERMOSTAT
R847A
T
T
L1
3
4
L2
LOAD
ADD
JUMPER
Material Number Input Voltage Frequency Switching Description Includes
R847A1085/U 120V 50 Hz; 60 Hz DPST or SPST This 120V, 50 Hz or 60 Hz Heavy Duty Switching Relay with integral transform,
and DPST or SPST line voltage relays, is used for 24 volt 2-wire thermostat control
of high-current loads such as cooling compressors.
Integral transformer,
enclosure
R856 Control Center
Provides 24 volt control of line voltage motors, fans, blowers, or
pumps up to 1 hp.
Integral 45 VA transformer to supply low voltage power for the
system.
Low voltage terminal strip for easy thermostat and panel
connections.
Application: Enclosed fan center for 24 volt control of a line voltage
motor, evaporator fan, or pump up to 1 horsepower. Includes wring
terminal board and 45 VA transformer.
Input Voltage: 120V
Frequency: 60 Hz
Coil Ratings: 6 VA (Sealed); 11 VA (inrush)
Coil Ratings Current: 0.22A
Electrical Ratings, Contacts: Horsepower – 3/4 hp N.O.; 1/2 hp N.C.
Contact Ratings (AFL): 14.0A N.O.; 10.0A N.C. @ 120 Vac
Contact Ratings (ALR): 120 Vac – 84.0A N.C., 80.0A N.C.
Approximate, Dimensions: 7 1/8 in. high x 4 1/2 in. wide x 3 5/16 in.
deep (181 mm high x 114 mm wide x 84 mm deep)
Approvals, CSA: Certified: File No. LR95329-1
Approvals, Underwriters Laboratories Inc.: Listed: File No. E4436, Vol.
6 Sec. 9
Includes: External transformer, enclosure
Material Number Coil Ratings Voltage Switching
R856B1002/U 24 Vac SPST
Hydronic Switching Relays