Brochure
22 63-8702
T6 Thermostats
T6 Hydronic Thermostats
T6 Pro Hydronic Programmable Thermostat can be used to control the
ambient air temperature or floor temperature or both. You can choose
among the following temperature control modes:
A mode: Controls and displays the ambient air temperature only.
F mode: Controls and displays the floor temperature only using an
external floor temperature sensor. This control mode is suitable
for areas such as bathrooms where floor temperature could be
scheduled to be warm only during occupied, morning and evening
periods.
AF mode: Controls and displays the ambient air temperature as well
as maintains the floor temperature within desired floor temperature
limits using an external floor temperature sensor. Setting the
minimum and maximum floor temperature limits is a way to
enhance comfort and to protect the floor covering at the same time.
Dimensions Lead Length: 180 in. (4570 mm.) 10 kohm NTC thermistor
at 25 C
Programming Options: 7-day, 5-1-1, 5-2, non- programmable
Temperature Sensor Accuracy: ± 1.5 °F at 70 °F (0.85 °C at 21.0 °C)
Clock Accuracy:± 1 minute every month (30 days) at 77°F. ± 2 minutes
per month over the operating ambient temperature range.
Physical Dimensions: 4-1/16” H x 4-1/16” W x 1-5/32” D
103.5 mm H x 103.5 mm W x 29 mm D
Display Size: 5.44 sq. in.
Power Requirements: AA alkaline battery 2pcs. And/or
C-wire input: 18-30VAC; 50Hz-60Hz
Selectable Range Stops:
Max Heat:
A/AF mode: 40 to 90 °F (default 90 °F); 4.5 to 32.0 °C (default 32 °C)
F mode: 40 to 99 °F (default 85 °F); 4.5 to 38.0 °C (default 29.5°C)
Min Heat:
A/AF mode: 40 to 90 °F (default 50 °F); 4.5 to 32.0 °C (default 10 °C)
F mode: 40 to 99 °F (default 50 °F); 4.5 to 38.0 °C (default 10°C)
Min Floor Temp Limit: 40 to 89 °F (72 °F); 4.5 to 31.5 °C (22.2°C)
Max Floor Temp Limit: 50 to 99 °F (85 °F); 10 to 38 °C (29.5°C)
Freeze Protection Temperature:
A Mode: 40 to 50 °F (40 °F); 4.5 to 10.0 °C (4.5 °C)
A/AF Mode: 40 °F (4.5 °C) to Min. Floor Temp. Limit
F Mode: 40 °F (4.5 °C) to Min. Heat Temp. Setpoint
Operating Ambient Temperature: 37 to 102 °F (2.8 to 38.9 °C)
Shipping Temperature: -20 to 120 °F (-28.9 to 48.9 °C)
Operating Relative Humidity: 5% to 90% (non-condensing)
Color: White
Material Number Description Program Options Power
Method
Display
Size
Stages External Sensor
Available
TH6100AF2004/U T6 Pro Hydronic Programmable Thermostat can be used to
control hot water heat systems by sensing the ambient air
temperature, floor temperature, or both. Wired floor sensor
included
7-Day, 5-1-1, 5-2,
non-programmable
Battery or
Hardwired
5.44 sq.in Up to 1 heat only. Hot
water, and steam
Floor Sensor
(included)