Install Instructions
ERV/HRV Ventilation Systems 69-2480EF—19 21
Installation Steps (continued)
5
Installing the condensation drain line
Insert the threaded drain adapter through the bottom of 
the unit and hand tighten the plastic nut supplied with 
the drain kit. 
Use a wrench to tighten the nut another half turn to  
ensure a complete seal. 
Install the condensate tubing by pushing the clear 
plastic tubing over the drain adapter. 
Make a condensate trap by looping the clear plastic 
tubing. This loop will prevent foul odors from entering 
the unit.
Use a condensate pump if you don’t have access to  
the floor drain.
Drainless Application
NOTE: If installing an ERV unit (VNT5150E1000, VNT5200E1000, VNT5070E1000) in a region where 
the outdoor temperature does not drop below freezing, the condensate drain line does not need 
to be installed and the unit may be installed as a drainless application.
1. Insert the threaded drain adapter through the bottom 
  of the ERV with the drain connection inside of the unit 
  as shown in the figure.
2. Fit the rubber washer over the drain adapter and then 
  attach the plastic nut.
3. Hand tighten the plastic nut supplied with the drain kit.
4. Use a wrench to tighten the nut another half turn to 
  ensure a complete seal.
5. Attach the drain cap to the drain adapter inside the 
 unit.