Submittal Sheet
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
www.resideo.com
68-3078EF—02 M.S. Rev. 09-21 | Printed in United States
© 2021 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from
Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Tous droits réservés. La marque de commerce Honeywell Home est utilisée avec l’autorisation d’Honeywell International,
Inc. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.
Removable Duct Collars
Spend less time on the ladder by easily connecting the
ductwork to the collars away from the unit before it’s hung,
and then sliding the collars back into place once ducted.
Intuitive Balancing
Two variable-speed motors — one for each air stream — work
with the integrated speed control so installers can adjust
the speed of each motor up and down to easily balance the
system. This eliminates the need for adjusting dampers.
Adjustable Hanging Straps
Just like tightening or loosening straps on a backpack, these
straps make it easy to raise, lower and level the unit into place
Ventilation Performance VNT5150E
External Static Pressure Net Supply Air Flow
Pa in w.c. L/s CFM
25 0.1 97 207
50 0.2 89 189
75 0.3 88 187
100 0.4 75 159
125 0.5 70 148
150 0.6 62 131
175 0.7 55 116
200 0.8 49 104
225 0.9 42 90
250 1.0 37 77
275 1.1 32 68
VNT5150E1000
AIR FLOW (L/S)
0
0.2
0.4
0.6
0.8
1
1.2
050 100 150 200 250
0
25
50
75
100
125
150
175
200
225
250
275
300
0102030405060708090100 110
NET SUPPLY AIR FLOW
AIR FLOW (CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
EXTERNAL
STATIC
PRESSURE
(PA)
M32997
Push Through—Operation System
Outside air is pushed through the heat exchanger, which acts
as a noise reducer. This process is very silent and provides
you with better home comfort.
FRESH AIR
FROM
OUTSIDE
FRESH AIR
FROM
OUTSIDE
EXHAUST
AIR TO
OUTSIDE
EXHAUST
AIR FROM
HOME
M32359A
Proportional Defrost—Operation System
The defrost energy is controlled by the outdoor air
temperature. The motor speed essentially increases as
outdoor temperature drops to provide increased defrost
capability.
WARNING: Installation must be performed by a
qualified service technician and must comply with
local codes. Remove power to the device before
installing or servicing the device. Failure to
connect the device according to these instructions
may result in damage to the device or the controls.
Energy Performance VNT5150E
Supply Temperature Net Supply Air Flow Average Power Sensible Recovery Apparent Sensible
°C °F L/s CFM Watts Efficiency (%) Effectiveness (%)
Heating
0 32 24 51 58 65 76
0 32 38 80 76 65 73
0 32 56 118 96 62 70
15 5 26 55 59 52 78
Cooling
35 95 30 64 66
Total Recovery Efficiency = 34%