Product Overview

V8043A, E, F 5000 SERIES ZONE VALVES
95C-10932—04 4
Fig. 6. Typical Wiring for V8043E, V8044E.
Fig. 7. Typical Wiring for V8043F.
Fig. 8. T822 Thermostat, V8043A Valve Hookup.
Fig. 9. T822, V8043E zone hookup for gas or oil. No
domestic hot water.
Fig. 10. T822, V8043E zone hookup for gas or oil with or
without domestic hot water. Without domestic hot
water, use L8148J for gas, and L8148A for oil. With
domestic hot water, use L8124E for gas, and L8124A or
C for oil.
AUXILIARY
SWITCH
MOTOR
YELLOW
LEADS
TO CIRCULATOR
OR ANOTHER VALVE
RED LEADS
THERMOSTAT
(TYPICALLY T87F)
TO
LINE
M5953
R
L1
(HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
END SWITCH
TO CIRCULATOR
OR ANOTHER
VALVE
TH
TR
24V
TRANSFORMER
THERMOSTAT
(TYPICALLY T87F)
TH TR
M5952
L1
(HOT)
L2
1
1
2
2
2 2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.
T822 T822 T822
V8043A V8043A V8043A
M10168
L1
(HOT)
L2
1
1
2
2
3
2 2
3 3 3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
CONNECT V8043E RED LEADWIRES TO L1 (HOT) LINE AND
PRIMARY CONTROL.
T822 T822 T822
V8043E V8043E V8043E
M10169
TO OIL PRIMARY
CONTROL OR TO
TRANSFORMER
AND LOW VOLTAGE
GAS VALVE
L4006A
HIGH
LIMIT
CIRCULATOR
L1
(HOT)
L2
1
1
2
2
3
2 2
3 3 3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
CONNECT V8043E RED LEADWIRES TO AQUASTAT®.
T822 T822 T822
V8043E V8043E V8043E
M10170
CIRCULATOR
TT
1
2C1
TO BURNER
CONTROL
CIRCUIT
B1
B2
C2