Product Overview
Table Of Contents
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES
60-2133—12 6
How to Find Maximum Valve Operating
Temperature
The maximum operating temperature for motorized valves
depends on the maximum ambient temperature at the
valve location, and on the maximum fluid temperature.
Using the graph in Fig. 2, find the maximum valve
operating temperature as follows:
1. Measure the ambient temperature at the valve and
locate that temperature on the ambient temperature
scale on the graph.
2. Draw a line from the ambient temperature, parallel
with the fluid temperature scale, to the maximum
fluid temperature line.
3. Draw a line from that point down to the fluid tem-
perature scale to find the maximum operating tem-
perature. (Note the example shown by the dashed
line in Fig. 2)
To find the maximum ambient temperature for a valve
when the fluid temperature is known, reverse this
procedure.
Table 2. Replacement Powerheads.
Valve Model
Number Part Number
Electrical
Connection on
Which Side of
Manual Lever
Voltage (Vac)
and
Frequency
(Hz) Current Draw (A)
Type of
Electrical
Connection Motor
V4043A 40003916-022 Same 220/50, 240/60 0.04 18 in. (457 mm)
leads (conduit
opening)
Class F; plated
40003916-023 Same 240, 50 0.04
40003916-024 Same 120, 60 0.08
V4043B 40003916-030 Same 240, 60 0.04
40003916-031 Same 120, 60 0.08
40003916-042 Same 208, 60 0.04
V8043A 40003916-021 Same 24, 50/60 0.32 Class A
V8043B 40003916-027 Same 24, 50/60 0.32
V8043E 40003916-026 Same 24, 50/60 0.32
V8043F 40003916-048 Same 24, 50/60 0.32 Terminal Board
V4044A 40003916-034 Opposite 240, 50 0.04 18 in. (457 mm)
leads (conduit
opening)
Class F, plated
40003916-035 Opposite 220/50, 240/60 0.04
40003916-036 Opposite 120, 60 0.08 96 in. (2438 mm)
leads (conduit
opening)
40003916-047 Same 120, 60 0.08
V4044B 40003916-039 Opposite 220/50, 240/60 0.04 18 in. (457 mm)
leads (conduit
opening)
40003916-040 Opposite 120, 60 0.08
40003916-045 Same 120, 60 0.08
V8044A 40003916-032 Opposite 24, 50/60 0.32 18 in. (457 mm)
leads (conduit
opening)
Class A, plated
40003916-046 Same 24, 50/60 0.32
V8044B 40003916-037 Opposite 24, 50/60 0.32 18 in. (457 mm)
leads (conduit
opening)
40003916-044 Same 24, 50/60 0.32