Install Instructions
V4043 MOTORISED ZONE VALVE
© 2020 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
95C-10388—07 M.S. Rev. 03-20 | Printed in United States
NOTES:
a. Wiring diagrams show connections necessary to
a twin switched live output programmer, i.e. one
with separate control of heating and hot water.
b. If simple, single switched, live timeclock is used,
connect switched live supply to both room ther-
mostat and cylinder thermostat, e.g. connect
switched live to either terminal 4 or 6 at junction
box, then link 4 and 6 with a bridge wire.
c. If using boiler with integral programmer, refer to
boiler manufacturers instructions on wiring.
GENERAL
N.B. if using 6” wire, V4043H in S-Plan White wire is not
needed and must be made electrically safe.
CHECKOUT PROCEDURES
For SUNDIAL CONTROL PLANS or similar central heating
applications:
1. Check manual lever is in ‘AUTO’ position.
2. Check timeclock/programmer has power.
3. Check boiler is switched on and its thermostat set to
about 80° C.
(C & S PLAN) confirm correct hot water function as
follows:
1. Turn room thermostat right down or switch off heat-
ing at programmer. Ensure ‘Hot Water’ is ON at pro-
grammer.
2. Set cylinder thermostat to maximum.
3. Boiler should fire and pump should run. Feel pipe
approximately 12” from valve outlet port on cylinder
circuit; it should get hot.
(S PLAN) confirm correct heating function as follows:
1. Turn cylinder thermostat right down and switch hot
water off at programmer, if programmer enables
‘Heating Only’. Ensure heating is ON at programmer.
2. Set room thermostats to maximum.
3. Boiler should fire and pump should run. Feel pipe
approximately 12” from valve outlet port on radiator
circuit; it should get hot.
COMPLETION
Set both thermostats to temperatures required by
householder — recommended temperatures: 60° C for
cylinder thermostat and 20° C for room thermostat.
Full installation, wiring, and operating instructions for
Sundial Products are included in every pack. For special
wiring applications, contact your local Resideo Office for
the Sundial Wiring Booklet.
Whilst Resideo takes all reasonably practicable steps to
design and manufacture its products to comply with the
requirement of the Health and Safety at Work Act 1974, all
products must be properly installed and used. Purchasers
are reminded that their obligations under the Act are to
ensure that the installation and operation of such
products should be safe and without risk to health.
Resideo reserves the right at any time and without notice
to change any product or information contained in this
publication.